Electric field mitigation near over head power lines using voltage unbalance

Other Title(s)

التخفيف من المجال الكهربائي بالقرب من خطوط الطاقة باستخدام فرق الجهد السلبي

Joint Authors

Judi, Amr Muhammad Rifat
Abd al-Latif, Muhammad Ahmad Ali
Taj al-Din, al-Sayyid Muhammad Ahmad
Ibrahim, Khalid H.

Source

Fayoum University Journal of Engineering

Issue

Vol. 4, Issue 1 (30 Jun. 2021), pp.155-165, 11 p.

Publisher

Fayoum University Faculty of Engineering

Publication Date

2021-06-30

Country of Publication

Egypt

No. of Pages

11

Main Subjects

Electronic engineering

Topics

Abstract EN

A lot of people have to live near power lines, and there is strong evidence that electric fields around power lines may cause cancer as well as many other symptoms that humans can directly observe, such as poor short-term memory, chronic fatigue, depression, nausea, and rashes.

Hence, it is necessary to mitigate these fields to acceptable values to protect such groups.

There are already many conventional compensation techniques in electric field mitigation may be useful in areas where the space is available however in residence with high civil density other techniques should be introduced.

In the present paper, the self-compensation using voltage unbalance will be introduced.

The main concept of the research is that the electric field resulting from three-phase voltages is negligible as the separations among phases are too small.

However, in Overhead Transmission Lines the separations among conductors are determined based on the breakdown strength of air and cannot be changed widely.

On the other hand, this concept could be applied electrically not mechanically in overhead power lines by controlling the three-phase voltages to make it as if it were located as near as possible to each other, resulting in a lower electric field.

Genetic Algorithm (GA) is used to find the desired voltage unbalance achieving the electric field as minimum as possible in the residence area.

The proposed algorithm is applied to 11 kV line and the results show that the electric field is reduced to about 82% under the safe limit, which is considered a very good percentage compared to other techniques.

American Psychological Association (APA)

Abd al-Latif, Muhammad Ahmad Ali& Judi, Amr Muhammad Rifat& Taj al-Din, al-Sayyid Muhammad Ahmad& Ibrahim, Khalid H.. 2021. Electric field mitigation near over head power lines using voltage unbalance. Fayoum University Journal of Engineering،Vol. 4, no. 1, pp.155-165.
https://search.emarefa.net/detail/BIM-1370793

Modern Language Association (MLA)

Abd al-Latif, Muhammad Ahmad Ali…[et al.]. Electric field mitigation near over head power lines using voltage unbalance. Fayoum University Journal of Engineering Vol. 4, no. 1 (2021), pp.155-165.
https://search.emarefa.net/detail/BIM-1370793

American Medical Association (AMA)

Abd al-Latif, Muhammad Ahmad Ali& Judi, Amr Muhammad Rifat& Taj al-Din, al-Sayyid Muhammad Ahmad& Ibrahim, Khalid H.. Electric field mitigation near over head power lines using voltage unbalance. Fayoum University Journal of Engineering. 2021. Vol. 4, no. 1, pp.155-165.
https://search.emarefa.net/detail/BIM-1370793

Data Type

Journal Articles

Language

English

Notes

-

Record ID

BIM-1370793