Control of hydraulic transients in the water piping system in badra-pumping station No. 5

Other Title(s)

التحكم بتأثيرات المطرقة المائية في منظومة أنابيب الماء لمحطة ضخ بدرة رقم 5

Joint Authors

Jijan, Miqdam Tariq
al-Zubaydi, Dina Sadi Munim

Source

Nahrain University-College of Engineering Journal

Issue

Vol. 18, Issue 2 (31 Dec. 2015), pp.229-239, 11 p.

Publisher

Nahrain University College of Engineering

Publication Date

2015-12-31

Country of Publication

Iraq

No. of Pages

11

Main Subjects

Engineering & Technology Sciences (Multidisciplinary)

Abstract EN

In this paper, the surge tank utilization method was used to prevent the water hammer.

The study was conducted on a practical problem at pipelines and pumping station of Badra – pumping station No.

5, which is possessed to Iraqi General Company for Execution and Irrigation.

For this purpose, Surge2012 transient analysis software was used to achieve the best design and checking parameters.

The study recommends installing 2x14m3 closed surge tanks near to lifting station.

The outlet/inlet nozzle has to be of 300 mm diameter.

The initial air volume must be 5 m3 for each one.

All these parameters must be achieved to maintain a positive and negative pressure waves in pipe network system within accepted values.

American Psychological Association (APA)

Jijan, Miqdam Tariq& al-Zubaydi, Dina Sadi Munim. 2015. Control of hydraulic transients in the water piping system in badra-pumping station No. 5. Nahrain University-College of Engineering Journal،Vol. 18, no. 2, pp.229-239.
https://search.emarefa.net/detail/BIM-819083

Modern Language Association (MLA)

Jijan, Miqdam Tariq& al-Zubaydi, Dina Sadi Munim. Control of hydraulic transients in the water piping system in badra-pumping station No. 5. Nahrain University-College of Engineering Journal Vol. 18, no. 2 (Dec. 2015), pp.229-239.
https://search.emarefa.net/detail/BIM-819083

American Medical Association (AMA)

Jijan, Miqdam Tariq& al-Zubaydi, Dina Sadi Munim. Control of hydraulic transients in the water piping system in badra-pumping station No. 5. Nahrain University-College of Engineering Journal. 2015. Vol. 18, no. 2, pp.229-239.
https://search.emarefa.net/detail/BIM-819083

Data Type

Journal Articles

Language

English

Notes

Record ID

BIM-819083