Earth fault protection failure in the distribution transformer 110.4 kV supply

Joint Authors

Jasim, Muhammad S.
Abd al-Wahhab, Thamir Muhammad

Source

Engineering and Technology Journal

Issue

Vol. 36, Issue 4A (30 Apr. 2018), pp.391-400, 10 p.

Publisher

University of Technology

Publication Date

2018-04-30

Country of Publication

Iraq

No. of Pages

10

Main Subjects

Information Technology and Computer Science

Abstract EN

This research studies a miss-coordination problem in the protection of 11 kV distribution network in Iraq.

The problem arises when an underground cable is exposed to an earth fault at a location between the High Rupturing Capacity (HRC) fuses and the high voltage windings of the distribution transformer.

In this case, the protective relay of the main circuit breaker of the feeder operates at a time faster than the HRC fuses of the faulty transformer.

The distribution network considered in this work is an underground 11kV distribution network at Al-Rusafa General Directorate geographical region in Baghdad city.

The problem was studied using mathematical analysis and software analysis.

The mathematical results and the analysis of the simulated network using CYME 7.1 program show that the relay will operate before the HRC fuses as a response to an earth fault occurrence on that part of the network.

To solve this problem several solutions are proposed and discussed in this research.

American Psychological Association (APA)

Abd al-Wahhab, Thamir Muhammad& Jasim, Muhammad S.. 2018. Earth fault protection failure in the distribution transformer 110.4 kV supply. Engineering and Technology Journal،Vol. 36, no. 4A, pp.391-400.
https://search.emarefa.net/detail/BIM-832316

Modern Language Association (MLA)

Abd al-Wahhab, Thamir Muhammad& Jasim, Muhammad S.. Earth fault protection failure in the distribution transformer 110.4 kV supply. Engineering and Technology Journal Vol. 36, no. 4A (2018), pp.391-400.
https://search.emarefa.net/detail/BIM-832316

American Medical Association (AMA)

Abd al-Wahhab, Thamir Muhammad& Jasim, Muhammad S.. Earth fault protection failure in the distribution transformer 110.4 kV supply. Engineering and Technology Journal. 2018. Vol. 36, no. 4A, pp.391-400.
https://search.emarefa.net/detail/BIM-832316

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references : p. 400

Record ID

BIM-832316