System Efficiency of a Tap Transformer Based Grid Connection Topology Applied on a Direct Driven Generator for Wind Power

المؤلفون المشاركون

Eriksson, Sandra
Apelfröjd, Senad

المصدر

The Scientific World Journal

العدد

المجلد 2014، العدد 2014 (31 ديسمبر/كانون الأول 2014)، ص ص. 1-7، 7ص.

الناشر

Hindawi Publishing Corporation

تاريخ النشر

2014-08-31

دولة النشر

مصر

عدد الصفحات

7

التخصصات الرئيسية

الطب البشري
تكنولوجيا المعلومات وعلم الحاسوب

الملخص EN

Results from experiments on a tap transformer based grid connection system for a variable speed vertical axis wind turbine are presented.

The tap transformer based system topology consists of a passive diode rectifier, DC-link, IGBT inverter, LCL-filter, and tap transformer.

Full range variable speed operation is enabled by using the different step-up ratios of a tap transformer.

Simulations using MATLAB/Simulink have been performed in order to study the behavior of the system.

A full experimental set up of the system has been used in the laboratory study, where a clone of the on-site generator was driven by an induction motor and the system was connected to a resistive load to better evaluate the performance.

Furthermore, the system is run and evaluated for realistic wind speeds and variable speed operation.

For a more complete picture of the system performance, a case study using real site Weibull parameters is done, comparing different tap selection options.

The results show high system efficiency at nominal power and an increase in overall power output for full tap operation in comparison with the base case, a standard transformer.

In addition, the loss distribution at different wind speeds is shown, which highlights the dominant losses at low and high wind speeds.

Finally, means for further increasing the overall system efficiency are proposed.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

Apelfröjd, Senad& Eriksson, Sandra. 2014. System Efficiency of a Tap Transformer Based Grid Connection Topology Applied on a Direct Driven Generator for Wind Power. The Scientific World Journal،Vol. 2014, no. 2014, pp.1-7.
https://search.emarefa.net/detail/BIM-1051015

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

Apelfröjd, Senad& Eriksson, Sandra. System Efficiency of a Tap Transformer Based Grid Connection Topology Applied on a Direct Driven Generator for Wind Power. The Scientific World Journal No. 2014 (2014), pp.1-7.
https://search.emarefa.net/detail/BIM-1051015

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

Apelfröjd, Senad& Eriksson, Sandra. System Efficiency of a Tap Transformer Based Grid Connection Topology Applied on a Direct Driven Generator for Wind Power. The Scientific World Journal. 2014. Vol. 2014, no. 2014, pp.1-7.
https://search.emarefa.net/detail/BIM-1051015

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references

رقم السجل

BIM-1051015