OverUndervoltage and Undervoltage Shift of Hybrid Islanding Detection Method of Distributed Generation

المؤلفون المشاركون

Yingram, Manop
Premrudeepreechacharn, Suttichai

المصدر

The Scientific World Journal

العدد

المجلد 2015، العدد 2015 (31 ديسمبر/كانون الأول 2015)، ص ص. 1-11، 11ص.

الناشر

Hindawi Publishing Corporation

تاريخ النشر

2015-03-23

دولة النشر

مصر

عدد الصفحات

11

التخصصات الرئيسية

الطب البشري
تكنولوجيا المعلومات وعلم الحاسوب

الملخص EN

The mainly used local islanding detection methods may be classified as active and passive methods.

Passive methods do not perturb the system but they have larger nondetection zones, whereas active methods have smaller nondetection zones but they perturb the system.

In this paper, a new hybrid method is proposed to solve this problem.

An over/undervoltage (passive method) has been used to initiate an undervoltage shift (active method), which changes the undervoltage shift of inverter, when the passive method cannot have a clear discrimination between islanding and other events in the system.

Simulation results on MATLAB/SIMULINK show that over/undervoltage and undervoltage shifts of hybrid islanding detection method are very effective because they can determine anti-islanding condition very fast.

ΔP/P>38.41% could determine anti-islanding condition within 0.04 s; ΔP/P<-24.39% could determine anti-islanding condition within 0.04 s; -24.39%≤ΔP/P≤ 38.41% could determine anti-islanding condition within 0.08 s.

This method perturbed the system, only in the case of -24.39% ≤ΔP/P ≤38.41% at which the control system of inverter injected a signal of undervoltage shift as necessary to check if the occurrence condition was an islanding condition or not.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

Yingram, Manop& Premrudeepreechacharn, Suttichai. 2015. OverUndervoltage and Undervoltage Shift of Hybrid Islanding Detection Method of Distributed Generation. The Scientific World Journal،Vol. 2015, no. 2015, pp.1-11.
https://search.emarefa.net/detail/BIM-1078965

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

Yingram, Manop& Premrudeepreechacharn, Suttichai. OverUndervoltage and Undervoltage Shift of Hybrid Islanding Detection Method of Distributed Generation. The Scientific World Journal No. 2015 (2015), pp.1-11.
https://search.emarefa.net/detail/BIM-1078965

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

Yingram, Manop& Premrudeepreechacharn, Suttichai. OverUndervoltage and Undervoltage Shift of Hybrid Islanding Detection Method of Distributed Generation. The Scientific World Journal. 2015. Vol. 2015, no. 2015, pp.1-11.
https://search.emarefa.net/detail/BIM-1078965

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references

رقم السجل

BIM-1078965