Overvoltage and Insulation Coordination of Overhead Lines in Multiple-Terminal MMC-HVDC Link for Wind Power Delivery

المؤلفون المشاركون

He, Huiwen
Wang, Lei
Zhou, Peihong
Yan, Fei

المصدر

International Journal of Rotating Machinery

العدد

المجلد 2017، العدد 2017 (31 ديسمبر/كانون الأول 2017)، ص ص. 1-7، 7ص.

الناشر

Hindawi Publishing Corporation

تاريخ النشر

2017-10-25

دولة النشر

مصر

عدد الصفحات

7

التخصصات الرئيسية

هندسة ميكانيكية

الملخص EN

The voltage-sourced converter-based HVDC link, including the modular multilevel converter (MMC) configuration, is suitable for wind power, photovoltaic energy, and other kinds of new energy delivery and grid-connection.

Current studies are focused on the MMC principles and controls and few studies have been done on the overvoltage of transmission line for the MMC-HVDC link.

The main reason is that environmental factors have little effect on DC cables and the single-phase/pole fault rate is low.

But if the cables were replaced by the overhead lines, although the construction cost of the project would be greatly reduced, the single-pole ground fault rate would be much higher.

This paper analyzed the main overvoltage types in multiple-terminal MMC-HVDC network which transmit electric power by overhead lines.

Based on ±500 kV multiple-terminal MMC-HVDC for wind power delivery project, the transient simulation model was built and the overvoltage types mentioned above were studied.

The results showed that the most serious overvoltage was on the healthy adjacent line of the faulty line caused by the fault clearing of DC breaker.

Then the insulation coordination for overhead lines was conducted according to the overvoltage level.

The recommended clearance values were given.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

He, Huiwen& Wang, Lei& Zhou, Peihong& Yan, Fei. 2017. Overvoltage and Insulation Coordination of Overhead Lines in Multiple-Terminal MMC-HVDC Link for Wind Power Delivery. International Journal of Rotating Machinery،Vol. 2017, no. 2017, pp.1-7.
https://search.emarefa.net/detail/BIM-1169553

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

He, Huiwen…[et al.]. Overvoltage and Insulation Coordination of Overhead Lines in Multiple-Terminal MMC-HVDC Link for Wind Power Delivery. International Journal of Rotating Machinery No. 2017 (2017), pp.1-7.
https://search.emarefa.net/detail/BIM-1169553

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

He, Huiwen& Wang, Lei& Zhou, Peihong& Yan, Fei. Overvoltage and Insulation Coordination of Overhead Lines in Multiple-Terminal MMC-HVDC Link for Wind Power Delivery. International Journal of Rotating Machinery. 2017. Vol. 2017, no. 2017, pp.1-7.
https://search.emarefa.net/detail/BIM-1169553

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references

رقم السجل

BIM-1169553