Diagnosis for Conductor Breaks of Grounding Grids Based on the Wire Loop Method of the Transient Electromagnetic Method
المؤلفون المشاركون
Ji, Yanju
Yu, Shengbao
Dong, Guanliang
Liu, Nannan
Liu, Xiyang
Xu, Chang
Luan, Hui
المصدر
Mathematical Problems in Engineering
العدد
المجلد 2019، العدد 2019 (31 ديسمبر/كانون الأول 2019)، ص ص. 1-11، 11ص.
الناشر
Hindawi Publishing Corporation
تاريخ النشر
2019-03-20
دولة النشر
مصر
عدد الصفحات
11
التخصصات الرئيسية
الملخص EN
The wire loop method of the transient electromagnetic (TEM) method is used to nondestructively detect conductor breaks of grounding grid.
For this purpose, grounding grids serve as an underground wire loop, and the measuring points are arranged on the ground.
At each measuring point, a receiving loop is employed to detect the electromagnetic response generated by transmitting the current of the transmitting loop.
Conductor breaks can be diagnosed by analyzing the slices of the electromagnetic response.
We study the effect of loop size and height difference through the simulation of an intact 2×2 grounding grid, confirming that it is easier to obtain the topological structure using a small transmitting loop and a small height difference.
Furthermore, simulations of an intact 4×4 grounding grid and grids with different locations of conductor breaks are also conducted with a small transmitting loop.
It is easy to distinguish the topological structure of the grounding grid and the locations of conductor breaks.
Finally, the detection method is applied experimentally.
The experimental results confirm that the proposed method is an effective technique for conductor break diagnosis.
نمط استشهاد جمعية علماء النفس الأمريكية (APA)
Yu, Shengbao& Dong, Guanliang& Liu, Nannan& Liu, Xiyang& Xu, Chang& Ji, Yanju…[et al.]. 2019. Diagnosis for Conductor Breaks of Grounding Grids Based on the Wire Loop Method of the Transient Electromagnetic Method. Mathematical Problems in Engineering،Vol. 2019, no. 2019, pp.1-11.
https://search.emarefa.net/detail/BIM-1194367
نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)
Yu, Shengbao…[et al.]. Diagnosis for Conductor Breaks of Grounding Grids Based on the Wire Loop Method of the Transient Electromagnetic Method. Mathematical Problems in Engineering No. 2019 (2019), pp.1-11.
https://search.emarefa.net/detail/BIM-1194367
نمط استشهاد الجمعية الطبية الأمريكية (AMA)
Yu, Shengbao& Dong, Guanliang& Liu, Nannan& Liu, Xiyang& Xu, Chang& Ji, Yanju…[et al.]. Diagnosis for Conductor Breaks of Grounding Grids Based on the Wire Loop Method of the Transient Electromagnetic Method. Mathematical Problems in Engineering. 2019. Vol. 2019, no. 2019, pp.1-11.
https://search.emarefa.net/detail/BIM-1194367
نوع البيانات
مقالات
لغة النص
الإنجليزية
الملاحظات
Includes bibliographical references
رقم السجل
BIM-1194367
قاعدة معامل التأثير والاستشهادات المرجعية العربي "ارسيف Arcif"
أضخم قاعدة بيانات عربية للاستشهادات المرجعية للمجلات العلمية المحكمة الصادرة في العالم العربي
تقوم هذه الخدمة بالتحقق من التشابه أو الانتحال في الأبحاث والمقالات العلمية والأطروحات الجامعية والكتب والأبحاث باللغة العربية، وتحديد درجة التشابه أو أصالة الأعمال البحثية وحماية ملكيتها الفكرية. تعرف اكثر