Coordinated Control Using Backstepping of DFIG-Based Wind Turbine for Frequency Regulation in High Wind Energy Penetrated System

المؤلفون المشاركون

Essadki, Ahmed
Nasser, Tamou
Nadour, Mohamed

المصدر

Mathematical Problems in Engineering

العدد

المجلد 2020، العدد 2020 (31 ديسمبر/كانون الأول 2020)، ص ص. 1-16، 16ص.

الناشر

Hindawi Publishing Corporation

تاريخ النشر

2020-04-29

دولة النشر

مصر

عدد الصفحات

16

التخصصات الرئيسية

هندسة مدنية

الملخص EN

The expansion of renewable generation has raised some red flags in terms of power system stability, control, and management.

For instance, unlike traditional synchronous energy sources, the doubly-fed induction generator- (DFIG-) based wind turbines (WTs) do not instinctively act against frequency deviations.

In fact, the power electronics interfacing the generator, merely controlled to warrant maximum wind power conversion, make its output power and mechanical speed immune to the characteristics of the electric network frequency.

Moreover, significant wind power penetration (WPP) promotes the retirement of many traditional generation groups, consequently curtailing the power system corresponding inertia and displacing the primary reserves that are essential to retain the frequency within an acceptable range of variation.

This paper explores different control approaches, using backstepping, allowing DFIG-based WTs to engage actively in frequency regulation using a coordinated control of the rotor speed and pitch angle to regulate the system during both partial- and full-load operation modes.

The first method momentarily discharges part of the kinetic energy stored in the WT spinning masses, and the second method follows a deloaded operation characteristic, so as to keep a specific power reserve that can be automatically activated at the events of frequency excursions.

A study case considering an isolated power system that consists of synchronous generators, DFIG-based wind farm, static load, and a sudden frequency disturbance was performed.

The simulation result in a Matlab/Simulink environment highlights the robustness and capability of the coordinated control scheme to furnish, under variant operation conditions, active power aid, consequently lifting the frequency nadir up to a superior level than that obtained with 0% wind power penetration in the system.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

Nadour, Mohamed& Essadki, Ahmed& Nasser, Tamou. 2020. Coordinated Control Using Backstepping of DFIG-Based Wind Turbine for Frequency Regulation in High Wind Energy Penetrated System. Mathematical Problems in Engineering،Vol. 2020, no. 2020, pp.1-16.
https://search.emarefa.net/detail/BIM-1201006

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

Nadour, Mohamed…[et al.]. Coordinated Control Using Backstepping of DFIG-Based Wind Turbine for Frequency Regulation in High Wind Energy Penetrated System. Mathematical Problems in Engineering No. 2020 (2020), pp.1-16.
https://search.emarefa.net/detail/BIM-1201006

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

Nadour, Mohamed& Essadki, Ahmed& Nasser, Tamou. Coordinated Control Using Backstepping of DFIG-Based Wind Turbine for Frequency Regulation in High Wind Energy Penetrated System. Mathematical Problems in Engineering. 2020. Vol. 2020, no. 2020, pp.1-16.
https://search.emarefa.net/detail/BIM-1201006

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references

رقم السجل

BIM-1201006