Optimal location of UPFC based on sensitivity of CDF with power system’s stochasticity

المؤلفون المشاركون

Zhang, Ningyu
Zhao, Jingbo
Zhou, Qian

المصدر

Journal of Engineering Research

العدد

المجلد 9، العدد 2 (30 يونيو/حزيران 2021)، ص ص. 149-160، 12ص.

الناشر

جامعة الكويت مجلس النشر العلمي

تاريخ النشر

2021-06-30

دولة النشر

الكويت

عدد الصفحات

12

التخصصات الرئيسية

هندسة الطاقة

الملخص EN

In this paper, a stochastic sensitivity algorithm is introduced to optimize the location of unified power flow controller (UPFC) in large scale power grid.

the stochastic sensitivities are defined as the total operation cost of power system to control parameters of UPFC.

firstly, probability optimal power flow (POPF) model with power system's randomness is established.

then point estimate method (PEM) is utilized to solve the above problem, so that the stochastic sensitivities of UPFC in all possible transmission lines could be obtained.

finally, by sorting the influence degree of UPFC at different locations to cumulative distribution function (CDF) of operation cost, the optimal location for UPFC could be selected correspondingly.

to this end, IEEE-5 and IEEE-14 systems are employed to verify our proposed approach.

the results show that installing UPFC by the method in this paper could significantly reduce the probability distribution of operation cost in higher region.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

Zhang, Ningyu& Zhao, Jingbo& Zhou, Qian. 2021. Optimal location of UPFC based on sensitivity of CDF with power system’s stochasticity. Journal of Engineering Research،Vol. 9, no. 2, pp.149-160.
https://search.emarefa.net/detail/BIM-1494843

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

Zhang, Ningyu…[et al.]. Optimal location of UPFC based on sensitivity of CDF with power system’s stochasticity. Journal of Engineering Research Vol. 9, no. 2 (Jun. 2021), pp.149-160.
https://search.emarefa.net/detail/BIM-1494843

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

Zhang, Ningyu& Zhao, Jingbo& Zhou, Qian. Optimal location of UPFC based on sensitivity of CDF with power system’s stochasticity. Journal of Engineering Research. 2021. Vol. 9, no. 2, pp.149-160.
https://search.emarefa.net/detail/BIM-1494843

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references : p. 160

رقم السجل

BIM-1494843