Assessing the risk of failure due to particle contamination in GIS under various coefficient of restitutions
المؤلفون المشاركون
Kumar, G. V. Nagesh
Jinka, Amarnath
المصدر
العدد
المجلد 10، العدد 3 (30 سبتمبر/أيلول 2014)، ص ص. 331-343، 13ص.
الناشر
تاريخ النشر
2014-09-30
دولة النشر
الجزائر
عدد الصفحات
13
التخصصات الرئيسية
الموضوعات
الملخص EN
The development of compressed gas insulated switchgear (GIS) equipment has progressed rapidly.
Conducting particles in transmission and switching equipment insulated by compressed sulphur hexafluoride (SF6) can result in loss of as much as 90% of the gas dielectric strength.
These particles may be free to move in the electric field or may be fixed on the conductors, thus enhancing local surface fields.
In a horizontal coaxial system with particles resting on the inside surface of the enclosure, the motion of such particles is random but the randomness depends on the coefficient of restitution and angle of incidence when approaching the coaxial conductors.
The power industry has utilized several methods to control and minimize the effect of particle contamination in GIS.
One such technique is to apply a dielectric (high resistivity) coating to the inside surface of the outer GIS enclosure.
The electric field necessary to lift a particle resting on the inside surface of a GIS enclosure is much increased due to the coating.
The simulation of the particle movement was carried under different Coefficient of Restitutions for coated busduct.
The results have been presented and analyzed.
نمط استشهاد جمعية علماء النفس الأمريكية (APA)
Kumar, G. V. Nagesh& Jinka, Amarnath. 2014. Assessing the risk of failure due to particle contamination in GIS under various coefficient of restitutions. Journal of Electrical Systems،Vol. 10, no. 3, pp.331-343.
https://search.emarefa.net/detail/BIM-399229
نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)
Kumar, G. V. Nagesh& Jinka, Amarnath. Assessing the risk of failure due to particle contamination in GIS under various coefficient of restitutions. Journal of Electrical Systems Vol. 10, no. 3 (2014), pp.331-343.
https://search.emarefa.net/detail/BIM-399229
نمط استشهاد الجمعية الطبية الأمريكية (AMA)
Kumar, G. V. Nagesh& Jinka, Amarnath. Assessing the risk of failure due to particle contamination in GIS under various coefficient of restitutions. Journal of Electrical Systems. 2014. Vol. 10, no. 3, pp.331-343.
https://search.emarefa.net/detail/BIM-399229
نوع البيانات
مقالات
لغة النص
الإنجليزية
الملاحظات
Includes bibliographical references : p. 343
رقم السجل
BIM-399229
قاعدة معامل التأثير والاستشهادات المرجعية العربي "ارسيف Arcif"
أضخم قاعدة بيانات عربية للاستشهادات المرجعية للمجلات العلمية المحكمة الصادرة في العالم العربي
تقوم هذه الخدمة بالتحقق من التشابه أو الانتحال في الأبحاث والمقالات العلمية والأطروحات الجامعية والكتب والأبحاث باللغة العربية، وتحديد درجة التشابه أو أصالة الأعمال البحثية وحماية ملكيتها الفكرية. تعرف اكثر