Abruption Cross-Section and Bending Change of ACSR Energy Lines in Fire Environment

المؤلفون المشاركون

Polykrati, A. D.
Anagnostatos, S. D.
Bourkas, P. D.
Koufakis, E. I.
Halevidis, C. D.

المصدر

Advances in Mechanical Engineering

العدد

المجلد 2010، العدد 2010 (31 ديسمبر/كانون الأول 2010)، ص ص. 1-5، 5ص.

الناشر

Hindawi Publishing Corporation

تاريخ النشر

2010-12-13

دولة النشر

مصر

عدد الصفحات

5

التخصصات الرئيسية

هندسة ميكانيكية

الملخص EN

An ACSR (Aluminum Conductors Steel Reinforced) power line, when it lies in a fire environment, can manifest a permanent elongation and change in bending, as when the conductors attain a temperature of over 500°C, a drastic fall of the mechanical strength of the steel core is caused.

This work is a study about the conductor cross-section at the position of the abruption, in case it occurs.

This cross section appears to be approximately 62.5% of the original value.

Subsequently, two approximative methods of calculating the bending change of overhead lines are shown.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

Halevidis, C. D.& Anagnostatos, S. D.& Polykrati, A. D.& Koufakis, E. I.& Bourkas, P. D.. 2010. Abruption Cross-Section and Bending Change of ACSR Energy Lines in Fire Environment. Advances in Mechanical Engineering،Vol. 2010, no. 2010, pp.1-5.
https://search.emarefa.net/detail/BIM-460891

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

Halevidis, C. D.…[et al.]. Abruption Cross-Section and Bending Change of ACSR Energy Lines in Fire Environment. Advances in Mechanical Engineering No. 2010 (2010), pp.1-5.
https://search.emarefa.net/detail/BIM-460891

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

Halevidis, C. D.& Anagnostatos, S. D.& Polykrati, A. D.& Koufakis, E. I.& Bourkas, P. D.. Abruption Cross-Section and Bending Change of ACSR Energy Lines in Fire Environment. Advances in Mechanical Engineering. 2010. Vol. 2010, no. 2010, pp.1-5.
https://search.emarefa.net/detail/BIM-460891

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references

رقم السجل

BIM-460891