Selection of Design Parameters to Reduce the Zero-Sequence Circulating Current Flow in Parallel Operation of DC Linked Multiple Shunt APF Units

المؤلفون المشاركون

Khadem, Shafiuzzaman K.
Basu, Malabika
Conlon, Michael F.

المصدر

Advances in Power Electronics

العدد

المجلد 2013، العدد 2013 (31 ديسمبر/كانون الأول 2013)، ص ص. 1-13، 13ص.

الناشر

Hindawi Publishing Corporation

تاريخ النشر

2013-12-08

دولة النشر

مصر

عدد الصفحات

13

التخصصات الرئيسية

هندسة كهربائية

الملخص EN

Capacity enhancement and operational flexibility are two of the important limitations of the centralized shunt APF (APFsh) unit.

These limitations can be conquered by the operation of multiple APF units in parallel and connected back to back by a common DC link capacitor.

In that case, a circulating current (CC) flows within the APFsh units.

This CC flow becomes out of control when the APFsh units operate in hysteresis based current controlled mode.

One of the difficulties of this CC flow control or reduction is the variable switching frequency of the APFsh units.

In this paper, the model for CC flow is derived by the switching dynamics study of the APFsh units.

It is found that the selection of design parameters plays an important role in the amount of CC flow.

Detailed simulation, analysis, and real-time performance show how the selection of design parameters affects the CC flow and the reduction of CC flow can also be achieved at an acceptable level by the proper selection of design parameters.

نمط استشهاد جمعية علماء النفس الأمريكية (APA)

Khadem, Shafiuzzaman K.& Basu, Malabika& Conlon, Michael F.. 2013. Selection of Design Parameters to Reduce the Zero-Sequence Circulating Current Flow in Parallel Operation of DC Linked Multiple Shunt APF Units. Advances in Power Electronics،Vol. 2013, no. 2013, pp.1-13.
https://search.emarefa.net/detail/BIM-467586

نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)

Khadem, Shafiuzzaman K.…[et al.]. Selection of Design Parameters to Reduce the Zero-Sequence Circulating Current Flow in Parallel Operation of DC Linked Multiple Shunt APF Units. Advances in Power Electronics No. 2013 (2013), pp.1-13.
https://search.emarefa.net/detail/BIM-467586

نمط استشهاد الجمعية الطبية الأمريكية (AMA)

Khadem, Shafiuzzaman K.& Basu, Malabika& Conlon, Michael F.. Selection of Design Parameters to Reduce the Zero-Sequence Circulating Current Flow in Parallel Operation of DC Linked Multiple Shunt APF Units. Advances in Power Electronics. 2013. Vol. 2013, no. 2013, pp.1-13.
https://search.emarefa.net/detail/BIM-467586

نوع البيانات

مقالات

لغة النص

الإنجليزية

الملاحظات

Includes bibliographical references

رقم السجل

BIM-467586