In Situ Determination of Thermal Resistivity of Soil : Case Study of Olorunsogo Power Plant, Southwestern Nigeria
المؤلفون المشاركون
Sanuade, Oluseun Adetola
Oladunjoye, Michael Adeyinka
المصدر
العدد
المجلد 2012، العدد 2012 (31 ديسمبر/كانون الأول 2012)، ص ص. 1-14، 14ص.
الناشر
Hindawi Publishing Corporation
تاريخ النشر
2012-07-12
دولة النشر
مصر
عدد الصفحات
14
التخصصات الرئيسية
الملخص EN
This study measured in situ the thermal resistivity of soils at Olorunsogo Gas Turbine Power Station (335 MW Phase 1) which is located in Ogun State, Southwestern Nigeria.
Ten pits, each of about 1.5 m below the ground surface, were established in and around the power plant in order to measure the thermal resistivity of soils in situ.
A KD 2-Pro was used for the in situ measurement of thermal properties.
Samples were also collected from the ten pits for laboratory determination of the physical parameters that influence thermal resistivity.
The samples were subjected to grain size distribution analysis, compaction, specific gravity and porosity tests, moisture content determination, and XRD analysis.
Also, thermal resistivity values were calculated by an algorithm using grain size distribution, dry density, and moisture content for comparison with the in situ values.
The results show that thermal resistivity values range from 34.07 to 71.88°C-cm/W with an average of 56.43°C-cm/W which falls below the permissible value of 90°C-cm/W for geomaterials.
Also, the physical parameters such as moisture content, porosity, degree of saturation, and dry density vary from 13.00 to 16.20%, 39.74 to 45.64%, 40.72 to 63.52%, and 1725.05 to 1930.00 Kg/m3, respectively.
The temperature ranges from 28.92 to 35.39°C with an average of 32.11°C in the study area.
The calculated thermal resistivity from an algorithm was found to vary from 48.43 to 81.22°C-cm/W with an average of 65.56°C-cm/W which is close to the thermal resistivity values measured in situ.
Good correlation exists between the in situ thermal resistivity and calculated thermal resistivity with R=+0.85 suggesting that both methods are reliable.
نمط استشهاد جمعية علماء النفس الأمريكية (APA)
Oladunjoye, Michael Adeyinka& Sanuade, Oluseun Adetola. 2012. In Situ Determination of Thermal Resistivity of Soil : Case Study of Olorunsogo Power Plant, Southwestern Nigeria. ISRN Civil Engineering،Vol. 2012, no. 2012, pp.1-14.
https://search.emarefa.net/detail/BIM-483333
نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)
Oladunjoye, Michael Adeyinka& Sanuade, Oluseun Adetola. In Situ Determination of Thermal Resistivity of Soil : Case Study of Olorunsogo Power Plant, Southwestern Nigeria. ISRN Civil Engineering No. 2012 (2012), pp.1-14.
https://search.emarefa.net/detail/BIM-483333
نمط استشهاد الجمعية الطبية الأمريكية (AMA)
Oladunjoye, Michael Adeyinka& Sanuade, Oluseun Adetola. In Situ Determination of Thermal Resistivity of Soil : Case Study of Olorunsogo Power Plant, Southwestern Nigeria. ISRN Civil Engineering. 2012. Vol. 2012, no. 2012, pp.1-14.
https://search.emarefa.net/detail/BIM-483333
نوع البيانات
مقالات
لغة النص
الإنجليزية
الملاحظات
Includes bibliographical references
رقم السجل
BIM-483333
قاعدة معامل التأثير والاستشهادات المرجعية العربي "ارسيف Arcif"
أضخم قاعدة بيانات عربية للاستشهادات المرجعية للمجلات العلمية المحكمة الصادرة في العالم العربي
![](/images/ebook-kashef.png)
تقوم هذه الخدمة بالتحقق من التشابه أو الانتحال في الأبحاث والمقالات العلمية والأطروحات الجامعية والكتب والأبحاث باللغة العربية، وتحديد درجة التشابه أو أصالة الأعمال البحثية وحماية ملكيتها الفكرية. تعرف اكثر
![](/images/kashef-image.png)