Study of (D-STATCOM)‎ impact in a grid connected (SCWEG)‎ under symmetrical fault

Joint Authors

Ibrahim, Ghadah Mahmud
Ahmad, Muhammad Kamal Muhammad
al-Sayyid, Muhammad Ibrahim

Source

Journal of al Azhar University : Engineering Sector

Issue

Vol. 14, Issue 52 (31 Jul. 2019), pp.926-937, 12 p.

Publisher

al-Azhar University Faculty of Engineering

Publication Date

2019-07-31

Country of Publication

Egypt

No. of Pages

12

Main Subjects

Electronic engineering

Topics

Abstract AR

في هذا البحث تم التركيز على تحسين عدم الاستقرار في الجهد و اداء توربينات الرياح التى تحتوى على المولد الحثى ذو القفص السنجابي و ذلك في حاله حدوث خطا و ذلك باستخدام المعوض التوزيعي الساكن (D-STATCOM) و تحسين كفائه النظام من خلاله.

Abstract EN


This paper provides an optimized (Distributed STATCOM) control for wind electric
generator.

The transient behavior of squirrel cage wind electric generator (SCWEG) can be
improved by injecting large amounts of reactive component during the fault recovery.

This
System requires a high dynamic converter, which able to work under abnormal conditions.


The reactive power demand, which is necessary for fixed- speed wind turbine system
(FSWTS) during faults is not met by capacitor banks installed near (SCWEG).

This paper
analyzes the impact of (D- STATCOM) in a grid connected (SCWEG) under fault and offers
study of the whole performance of the system which can be improved by means of
Distributed Static Synchronous Compensator (D-STATCOM).

It is used for restoring the
voltage at generator terminals under fault conditions was occurred.

Simulation was carried out
by MATLAB SIMULINK under abnormal conditions.

Both real and reactive powers confirm
that the (D- STATCOM) has good performance with (SCWEG), and the voltage profile is
improved, the stability is increased and the performance of the complete system is improved.



American Psychological Association (APA)

Ibrahim, Ghadah Mahmud& Ahmad, Muhammad Kamal Muhammad& al-Sayyid, Muhammad Ibrahim. 2019. Study of (D-STATCOM) impact in a grid connected (SCWEG) under symmetrical fault. Journal of al Azhar University : Engineering Sector،Vol. 14, no. 52, pp.926-937.
https://search.emarefa.net/detail/BIM-1022804

Modern Language Association (MLA)

Ibrahim, Ghadah Mahmud…[et al.]. Study of (D-STATCOM) impact in a grid connected (SCWEG) under symmetrical fault. Journal of al Azhar University : Engineering Sector Vol. 14, no. 52 (Jul. 2019), pp.926-937.
https://search.emarefa.net/detail/BIM-1022804

American Medical Association (AMA)

Ibrahim, Ghadah Mahmud& Ahmad, Muhammad Kamal Muhammad& al-Sayyid, Muhammad Ibrahim. Study of (D-STATCOM) impact in a grid connected (SCWEG) under symmetrical fault. Journal of al Azhar University : Engineering Sector. 2019. Vol. 14, no. 52, pp.926-937.
https://search.emarefa.net/detail/BIM-1022804

Data Type

Journal Articles

Language

English

Notes

-

Record ID

BIM-1022804