Abstract EN

In order to avoid the deficiencies of conventional high voltage circuit breaker mechanical properties detection methods, a new algorithm based on image block matching with diamond search strategy is presented in this paper.

The motion of auxiliary mark on the pull rod or shaft is firstly recorded by a high-speed and high-definition digital camera when the circuit breaker is open or close.

Then the motion trajectory is acquired through diamond image block matching method.

The mechanical parameters, such as travel and open and close velocity, are calculated according to the travel-time curve of the circuit breaker.

Finally, evaluation model is constructed taking mechanical parameters characteristic values as inputs of ELM.

Comparing to the existing techniques, our method is a noncontact measurement based on computer vision.

It is easy and convenient for practical application since it need not any electrical and mechanical connection to the breaker.

Another advantage of our method is that it can obtain the line and angle displacement simultaneously.

The experiment results on the circuit breaker of 220 kv show that our method is effective for breaker mechanical properties detection.

American Psychological Association (APA)

Niu, Weihua& Liang, Guishu& Yuan, Hejin& Li, Baoshu. 2016. A Fault Diagnosis Method of High Voltage Circuit Breaker Based on Moving Contact Motion Trajectory and ELM. Mathematical Problems in Engineering،Vol. 2016, no. 2016, pp.1-10.
https://search.emarefa.net/detail/BIM-1112011

Modern Language Association (MLA)

Niu, Weihua…[et al.]. A Fault Diagnosis Method of High Voltage Circuit Breaker Based on Moving Contact Motion Trajectory and ELM. Mathematical Problems in Engineering No. 2016 (2016), pp.1-10.
https://search.emarefa.net/detail/BIM-1112011

American Medical Association (AMA)

Niu, Weihua& Liang, Guishu& Yuan, Hejin& Li, Baoshu. A Fault Diagnosis Method of High Voltage Circuit Breaker Based on Moving Contact Motion Trajectory and ELM. Mathematical Problems in Engineering. 2016. Vol. 2016, no. 2016, pp.1-10.
https://search.emarefa.net/detail/BIM-1112011

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references

Record ID

BIM-1112011