Elimination of the Impact Produced by DG Units on the Voltage Profile of Distribution Networks

Joint Authors

Cherkaoui, Abdeljabbar
Ouali, Saad

Source

Journal of Applied Mathematics

Issue

Vol. 2020, Issue 2020 (31 Dec. 2020), pp.1-8, 8 p.

Publisher

Hindawi Publishing Corporation

Publication Date

2020-08-18

Country of Publication

Egypt

No. of Pages

8

Main Subjects

Mathematics

Abstract EN

In this paper, an alternative strategy for real-time control of active distribution network voltage is developed, not by controlling the bus voltage as in the various centralized, decentralized, and local approaches presented in literature but rather by only eliminating the impact produced by active and reactive power of distributed generation (DG) units on the voltage of all network nodes and keeping the traditional voltage control systems dealing with the same constraints of passive systems.

In literature, voltage deterioration introduced by DGs has been reported as one of the main obstacles for the interconnection of large amounts of DG units to the existing networks.

In this paper, the novel control strategy is based on a sensitivity formula developed to calculate the compensation needed for additional distributed flexible AC transmission system (D-FACTS) devices to push and pull the exact reactive power and to eliminate the impact produced by DGs on the network voltage profile.

The criteria of the allocation of the var devices and the required network reinforcement are developed in this paper, considering all possible topology structures, and an innovative codification method is introduced to reduce the needed computation time and communication data to actualize the sensitivity coefficients and get the proposed control approach flexible with network topology reconfiguration.

The risk of the conflict of the proposed control system with the traditional voltage equipment is reduced due to the fast capability of D-FACTS devices to regulate their reactive power in finer granularity.

A case study of two meshed IEEE 15-bus feeders is introduced to compare the voltage behavior with and without the presence of DG units and to evaluate the total system losses.

The proposed method could be used for the interconnection of the first generation units in emerging networks, which does not yet have an active voltage control strategy, as it could be used for DG units not able to be connected to existing centralized control systems and it could also be used as the principal voltage control strategy, with the extension for several neighboring units and the preservation of the traditional voltage control systems.

American Psychological Association (APA)

Ouali, Saad& Cherkaoui, Abdeljabbar. 2020. Elimination of the Impact Produced by DG Units on the Voltage Profile of Distribution Networks. Journal of Applied Mathematics،Vol. 2020, no. 2020, pp.1-8.
https://search.emarefa.net/detail/BIM-1174458

Modern Language Association (MLA)

Ouali, Saad& Cherkaoui, Abdeljabbar. Elimination of the Impact Produced by DG Units on the Voltage Profile of Distribution Networks. Journal of Applied Mathematics No. 2020 (2020), pp.1-8.
https://search.emarefa.net/detail/BIM-1174458

American Medical Association (AMA)

Ouali, Saad& Cherkaoui, Abdeljabbar. Elimination of the Impact Produced by DG Units on the Voltage Profile of Distribution Networks. Journal of Applied Mathematics. 2020. Vol. 2020, no. 2020, pp.1-8.
https://search.emarefa.net/detail/BIM-1174458

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references

Record ID

BIM-1174458