Wind Load Characteristics and Action Mechanism on Internal and External Surfaces of Super-Large Cooling Towers under Wind-Rain Combined Effects
Joint Authors
Ge, Y. J.
Ke, Shitang
Yu, Wenlin
Source
Mathematical Problems in Engineering
Issue
Vol. 2018, Issue 2018 (31 Dec. 2018), pp.1-22, 22 p.
Publisher
Hindawi Publishing Corporation
Publication Date
2018-07-08
Country of Publication
Egypt
No. of Pages
22
Main Subjects
Abstract EN
By focusing on wind-rain two-way coupling algorithm, simulation iterations of wind field and raindrops in the world highest cooling tower (210m) in northwest China were carried out using continuous phase and discrete phase models based on CFD numerical simulation.
Firstly, influence laws of 9 wind velocity-rainfall intensity combinations on wind-induced rainfall, raindrop additional force, and equivalent pressure coefficient on internal and external surface of the tower body were discussed.
On this basis, speed flow line, turbulence energy strength, raindrop running speed, and track on the tower body in the wind-rain coupling field were disclosed.
Finally, qualitative and quantitative contrastive analyses on wind pressure, rain pressure, and equivalent pressure coefficient on internal and external surfaces of the tower body were conducted under different working conditions.
Thus, the most unfavorable wind-rain combination was identified.
Calculation formulas of equivalent internal and external pressure coefficients of super-large cooling towers were fitted from nonlinear least square method.
Research results demonstrate that the 3D effect of equivalent internal and external pressure coefficients with considerations to wind-rain two-way coupling is more prominent.
Particularly, there is strong transition on the windward region of the external surface and leeside region at bottom of internal surface.
The quantity of caught raindrops on the structural surface is negatively related to wind velocity but is positively related to rainfall intensity.
Rain load and rainfall coefficients on the external surface are significantly higher than those on the internal surface.
Equivalent internal pressure coefficient has a sharp reduction on the leeside region under different working conditions.
Besides, equivalent internal pressure coefficient of different meridians decreases with the increase of height.
The maximum and minimum are -0.574 and -0.282, respectively.
The proposed equivalent internal and external pressure coefficients of super-large cooling tower can predict wind load under extreme climate conditions accurately.
American Psychological Association (APA)
Ke, Shitang& Yu, Wenlin& Ge, Y. J.. 2018. Wind Load Characteristics and Action Mechanism on Internal and External Surfaces of Super-Large Cooling Towers under Wind-Rain Combined Effects. Mathematical Problems in Engineering،Vol. 2018, no. 2018, pp.1-22.
https://search.emarefa.net/detail/BIM-1206543
Modern Language Association (MLA)
Ke, Shitang…[et al.]. Wind Load Characteristics and Action Mechanism on Internal and External Surfaces of Super-Large Cooling Towers under Wind-Rain Combined Effects. Mathematical Problems in Engineering No. 2018 (2018), pp.1-22.
https://search.emarefa.net/detail/BIM-1206543
American Medical Association (AMA)
Ke, Shitang& Yu, Wenlin& Ge, Y. J.. Wind Load Characteristics and Action Mechanism on Internal and External Surfaces of Super-Large Cooling Towers under Wind-Rain Combined Effects. Mathematical Problems in Engineering. 2018. Vol. 2018, no. 2018, pp.1-22.
https://search.emarefa.net/detail/BIM-1206543
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references
Record ID