Designing of high voltage cable bonding with intelligence algorithms to avoid cable insulation faults and electroshock in high voltage lines

Author

Akbal, Bahadır

Source

Journal of Engineering Research

Issue

Vol. 11, Issue 2 B (30 Jun. 2023), pp.158-172, 15 p.

Publisher

Kuwait University Academic Publication Council

Publication Date

2023-06-30

Country of Publication

Kuwait

No. of Pages

15

Main Subjects

Mechatronics Engineering

Abstract EN

Insulation faults are major problems in high-voltage cable lines.

The major factors in insulation faults are the harmonic currents and the metal sheath voltage (MV) that occur on the metal sheath of cables.

MV and harmonic distortion should be minimized to prevent insulation faults.

Thus, sectional solid bonding with different grounding resistance (SSBr) methods has been developed as a new bonding method for minimizing harmonic current and MV.

In addition, SSBr should be optimized by optimizing the minimum MV and harmonic distortion rate of high-voltage cables.

Inertia-weighted particle swarm optimization (iPSO), particle swarm optimization (PSO), genetic algorithm (GA), and differential evolution algorithm (DEA) are used for the optimization of SSBr, and three groups of prediction methods are used separately as objective functions of the optimization methods to determine the minimum MV and harmonic distortion; these groups include neural networks, hybrid neural networks, and regression methods.

Hybrid neural network with inertia-weighted particle swarm optimization (H-iPSO), linear regression, and feedforward backpropagation neural networks were selected from their groups according to training errors.

Solid bonding method, which is widely used for bonding high-voltage cables, is simulated in this study.

When solid bonding is used, the maximum harmonic distortion rate is measured as 8.15 %, and the maximum MV is measured as 1086 V.

When HiPSO is used as the prediction method and PSO is used as the optimization method, the maximum harmonic distortion rate is measured as 5.28 %, and the maximum MV is measured as 57 V.

Both insulation fault and electroshock can be prevented by the optimized SSBr method.

American Psychological Association (APA)

Akbal, Bahadır. 2023. Designing of high voltage cable bonding with intelligence algorithms to avoid cable insulation faults and electroshock in high voltage lines. Journal of Engineering Research،Vol. 11, no. 2 B, pp.158-172.
https://search.emarefa.net/detail/BIM-1604344

Modern Language Association (MLA)

Akbal, Bahadır. Designing of high voltage cable bonding with intelligence algorithms to avoid cable insulation faults and electroshock in high voltage lines. Journal of Engineering Research Vol. 11, no. 2 B (Jun. 2023), pp.158-172.
https://search.emarefa.net/detail/BIM-1604344

American Medical Association (AMA)

Akbal, Bahadır. Designing of high voltage cable bonding with intelligence algorithms to avoid cable insulation faults and electroshock in high voltage lines. Journal of Engineering Research. 2023. Vol. 11, no. 2 B, pp.158-172.
https://search.emarefa.net/detail/BIM-1604344

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references : p. 170-172

Record ID