Environmental assessment of alexandria medical research institute

Other Title(s)

التقييم البيئي لمعهد البحوث الطبية باللإسكندرية

Joint Authors

Isa, Basant Ali Yusuf A.
Abduh, Mamduh Hanafi M.
Mahmud, Aliyah Hanafi
al-Misiri, Mamduh Abd al-Munim

Source

Journal of King Abdul Aziz University : Meteorology, Environment and Arid land Agriculture Sciences

Issue

Vol. 20, Issue 1 (30 Jun. 2009), pp.83-103, 21 p.

Publisher

King Abdulaziz University Scientific Publishing Center

Publication Date

2009-06-30

Country of Publication

Saudi Arabia

No. of Pages

21

Main Subjects

Public Health

Topics

Abstract AR

في هذه الدراسة تم فحص بعض الخدمات البيئية الصحية في معهد البحوث الطبية، لإلقاء لإلقاء الضوء على الصحي و البيئي للمعهد، و قد أظهرت الدراسة من تقييم درجات الحرارة و الرطوبة على مدار العام، أن درجات الحرارة كانت تتراوح بين 19 و 28، في حين كانت الرطوبة تتراوح بين 67 % و 90 %، و بالنظر إلى مدى ملائمة التهوية الطبيعية في وحدات المستشفى، فإن عنابر المرضى المجانية، و المطبخ، و حجرة الغسول، و وحدة العلاج الكيميائي، و وحدة الجراحة (د) كانوا يعانون من سوء التهوية.

كذلك فإن بعضن أقسام المستشفى تعتمد تماما على مكيفات الهواء، في حين تعتمد أقسام أخرى اعتمادا تاما على التهوية الطبيعية، أما مدى ملائمة الإضاءة الطبيعية لحاجات المرضى و العاملين بأقسام و وحدات المستشفى المختلفة، فقد اعتمد ذلك على موقع القسم، أو الوحد ة، من حيث التعرض لضوء الشمس الطبيعي.

و كانت الوحدات ذات الإضاءة الطبيعية الضعيفة، هي عنابر المرضى المجانية، و المطبخ، و وحدة العلاج الكيماوي، و معمل البكتريولوجي، و كان استخدام الإضاءة الصناعية في معظم وحدات المستشفى شائعا خلال النهار، لتوفير قدر ملائم من الإضاءة، و أظهرت الدراسة فيما يختص بتقييم ممارسات التنظيف في وحدات المستشفى المختلفة، أن الوحدات التي لها أولوية في التنظيف هي الوحدات التي حققت فيها ممارسات التنظيف أعلى النتائج، و ذلك لأن المرضى في حجرات العمليات الجراحية، و وحدة القلب، و وحدة الغسيل الكلوي، يكونون أكثر عرضة للعدوى من المرضى الآخرين، و لذا فإن للنظافة في هذه الأماكن أولوية كبيرة، و بالرغم من اتباع أساليب متعددة على مستوى المستشفى ككل، و على مستوى الوحدات المختلفة للقضاء على ناقلات الأمراض من حشرات و قوارض، فإنه تمت ملاحظة وجود بعض الفئران و الصراصير و الذباب ؛ و قد يعود هذا لعدم الانتظام في استخدام وسائل القضاء على هذه الحشرات و القوارض من مبيدات و غيرها، و فيما يختص بخدمات المغسلة، فقد أظهرت الدراسة أنها غير ملائمة و لا تحقق الكثير من الاشتراطات الواجب توافرها في حجرة غسيل الملابس بالمستشفيات.

كان العاملون بالمغسلة في مجملهم مدربين تدريبا جيدا، و مع ذلك فلم يكونوا يقومون بفصل الملاءات و ملابس المرضى الشديدة التلوث، عن الملاءات و ملابس المرضى الأقل تلوثا أثناء عملية النقل ؛ كذلك لم يكن هناك عناية خاصة بالملاءات و ملابس المرضى التي قد تنقل العدوى ؛ أيضا لم يكن هناك استخدام للأكياس ذات الألوان المختلفة للتعرف على نوعية الغسيل، كما تنص منظمة الصحة العالمية ؛ و قد خلصت الدراسة الحالية إلى الكثير من النتائج، منها أن معهد البحوث الطبية كان على الغالب في حالة جيدة بالنسبة لمعظم الظروف الصحية البيئية، و إن كان هناك بعض القصور في بعض الخدمات الصحية البيئية.

Abstract EN

The evaluation of the temperature and humidity in the different sites of the Medical Research Institute (MRI) revealed that, all over the year, the temperature ranged between 19 and 28 degrees Centigrade, while the humidity ranged between 67 % and 90 % Ideally, temperature should be adjusted between 22 and 26°C, and relative humidity should be kept at 30 % to 60 %.

The adequacy of ventilation depended on the location of the hospital unit.

The cost-free wards, the kitchen, the laundry, the chemotherapy unit, and the surgery D ward had poor ventilation.

Some of the hospital departments depended on air conditioning systems and others made use of natural ventilation.

The light adequacy in the different departments and units depended on their site as regards exposure to the sunlight.

Examples for units with poor natural lighting were the cost-free wards, the kitchen, the chemotherapy unit, and the bacteriological laboratory.

Most of the units had to use artificial lighting during the daytime apart from the natural light to ensure adequate illumination.

The assessment of cleanliness revealed that the areas that had the priority for good cleaning practices had the highest score for cleanliness.

The patients in the operating theatre, cardiac care units and renal dialysis unit are more susceptible to infection than those in general wards.

Cleaning was therefore of particular importance in these areas.

Despite the use of vector control measures on both the hospital and unit levels, vectors were present in the hospital, e.g.

mice, cockroaches, and houseflies.

This may be due to the irregular use of pesticides and rat control measure.

The quality of the laundry services was found inadequate and did not fulfill many of the laundry requirements.

Color coding was not used in linen containers’ identification.

Furthermore, there was complete dependence on natural drying, as the dryer was not working.

There was also no bacterial evaluation for the laundry before and after washing.

The present study concluded that the Medical Research Institute was mostly good in its environmental conditions, except for some defects in certain services.

American Psychological Association (APA)

Isa, Basant Ali Yusuf A.& Abduh, Mamduh Hanafi M.& Mahmud, Aliyah Hanafi& al-Misiri, Mamduh Abd al-Munim. 2009. Environmental assessment of alexandria medical research institute. Journal of King Abdul Aziz University : Meteorology, Environment and Arid land Agriculture Sciences،Vol. 20, no. 1, pp.83-103.
https://search.emarefa.net/detail/BIM-327491

Modern Language Association (MLA)

Mahmud, Aliyah Hanafi…[et al.]. Environmental assessment of alexandria medical research institute. Journal of King Abdul Aziz University : Meteorology, Environment and Arid land Agriculture Sciences Vol. 20, no. 1 (2009), pp.83-103.
https://search.emarefa.net/detail/BIM-327491

American Medical Association (AMA)

Isa, Basant Ali Yusuf A.& Abduh, Mamduh Hanafi M.& Mahmud, Aliyah Hanafi& al-Misiri, Mamduh Abd al-Munim. Environmental assessment of alexandria medical research institute. Journal of King Abdul Aziz University : Meteorology, Environment and Arid land Agriculture Sciences. 2009. Vol. 20, no. 1, pp.83-103.
https://search.emarefa.net/detail/BIM-327491

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references : p. 99-101

Record ID

BIM-327491