Fault diagnosis system for power transformers

Other Title(s)

بناء نظام لتشخيص الأعطال لمحولات القوى الكهربائية

Joint Authors

Muhammad, al-Sayyid Abd al-Alim
Abd al-Aziz, al-Mutazz Yusuf
Mustafa, Amal Sayyid

Source

Journal of King Abdulaziz University : Engineering Sciences

Issue

Vol. 18, Issue 2 (31 Dec. 2007), pp.73-97, 25 p.

Publisher

King Abdulaziz University Scientific Publishing Center

Publication Date

2007-12-31

Country of Publication

Saudi Arabia

No. of Pages

25

Main Subjects

Electronic engineering

Topics

Abstract AR

يتناول هذا البحث بنا نظام لتشخيص الأعطال لمحولات القوى الكهربائية باستخدام الشبكات العصبية الاصطناعية.

صمم هذا النظام ليكتشف العطل, و يحدد مكانه, ثم يصنف هذا العطل.

و يتكون النظام المقترح من ثلاث مستويات متتابعة.

ففي الأول تتم عملية تجهيز البيانات, و في المستوى الثاني يتم تصميم شبكة عصبية بغرض اكتشاف العطل و تحديد جانب المحول الذي يقع به العطل, أما المستوى الثالث ففيه يتم بناء نظامي تشخيص فرعيين كل منهما يختص بجانب واحد من المحول, و يتكون كل نظام من شبكة عصبية لتصنيف (تحديد نوع) العطل, و يتبع هذه الشبكة أربع شبكات متوازية بهدف التعرف على الوجه الذي يقع به العطل.

يعتمد هذا النظام في أداءه على القياسات المباشرة من المحول, و هي : الجهد و التيار الثلاثي الأوجه للملف الابتدائي, بالإضافة إلى التيار الثلاثي للملف الثانوي.

تم استخدام برنامج الإلكترومغنطيسية العابرة في تمثيل منظومة و محولات القوى بشبكة الـ 500 كف بخط السد العالي.

و تم تمثيل جميع أنواع الأعطال في أماكن وقوع مختلفة من جانبي المحول و في لحظات زمنية مختلفة باستخدام هذا البرنامج.

و قد أثبتت نتائج الدراسة دقة و كفاءة أداء نظام التشخيص المقترح.

Abstract EN

This paper introduces an artificial neural network (ANN) based fault diagnosis system (FDS) for power transformers.

The system is designed to detect, localize and finally classify faults.

The proposed FDS consists of three hierarchical levels.

In the first level, a preprocessing procedure for input data is performed.

In the second level, an ANN is designed to detect the fault and localize its side.

In the third level, there are two sub-diagnosis systems.

Each system is dedicated to one side and consists of one ANN designed to classify the fault.

This ANN is also cascaded with four parallel ANN's utilized to identify the faulted phase.

The performance of FDS is evaluated using samples from local measurements (three-phase primary voltage and primary & secondary currents).

These samples were generated using the EMTP simulation of the High-Dam 15.75/500 kV transformer substation in the 500 kV Upper Egypt network.

Different fault types were simulated.

Fault location and incipience time were also considered.

Evaluation results proved that the performance of the proposed FDS is promising.

American Psychological Association (APA)

Muhammad, al-Sayyid Abd al-Alim& Abd al-Aziz, al-Mutazz Yusuf& Mustafa, Amal Sayyid. 2007. Fault diagnosis system for power transformers. Journal of King Abdulaziz University : Engineering Sciences،Vol. 18, no. 2, pp.73-97.
https://search.emarefa.net/detail/BIM-344366

Modern Language Association (MLA)

Muhammad, al-Sayyid Abd al-Alim…[et al.]. Fault diagnosis system for power transformers. Journal of King Abdulaziz University : Engineering Sciences Vol. 18, no. 2 (2007), pp.73-97.
https://search.emarefa.net/detail/BIM-344366

American Medical Association (AMA)

Muhammad, al-Sayyid Abd al-Alim& Abd al-Aziz, al-Mutazz Yusuf& Mustafa, Amal Sayyid. Fault diagnosis system for power transformers. Journal of King Abdulaziz University : Engineering Sciences. 2007. Vol. 18, no. 2, pp.73-97.
https://search.emarefa.net/detail/BIM-344366

Data Type

Journal Articles

Language

English

Notes

Includes appendices : p. 90-96

Record ID

BIM-344366