![](/images/graphics-bg.png)
Water treatment of cooling towers blowdown by reverse osmosis
Source
Issue
Vol. 11, Issue 2 (30 Jun. 2005), pp.421-428, 8 p.
Publisher
University of Baghdad College of Engineering
Publication Date
2005-06-30
Country of Publication
Iraq
No. of Pages
8
Main Subjects
Abstract EN
An experimental investigation was conducted to study the effect of operating parameters on the permeable conductivity and product rate were studied for reverse osmosis process.
The parameters studied were: - conductivity of feed water in the range of (1000-1500 us/cm), pH in the range of (4-10) and operating pressure in the range of (3-6 bar).
The best operating conditions, which lead to good quantity and quality for water product, are: (1000 us/cm) conductivity of feed water, (7) pH and (6 bar) operating pressure.
At these conditions the permeable conductivity is (52.905 us/cm) and the product rate is (328.143 1/hr).
American Psychological Association (APA)
al-Himiri, Adil& Biddai, Ammar A.. 2005. Water treatment of cooling towers blowdown by reverse osmosis. Journal of Engineering،Vol. 11, no. 2, pp.421-428.
https://search.emarefa.net/detail/BIM-360906
Modern Language Association (MLA)
al-Himiri, Adil& Biddai, Ammar A.. Water treatment of cooling towers blowdown by reverse osmosis. Journal of Engineering Vol. 11, no. 2 (Jun. 2005), pp.421-428.
https://search.emarefa.net/detail/BIM-360906
American Medical Association (AMA)
al-Himiri, Adil& Biddai, Ammar A.. Water treatment of cooling towers blowdown by reverse osmosis. Journal of Engineering. 2005. Vol. 11, no. 2, pp.421-428.
https://search.emarefa.net/detail/BIM-360906
Data Type
Journal Articles
Language
English
Notes
Includes appendices : p. 425-428
Record ID