Assessment the potential of scale formation and the corrosivity of Al-Najebia thermal power plant cooling system water

Other Title(s)

تقييم إمكانية الماء المستعمل في نظام تبريد محطة كهرباء النجيبية على تكوين الترسبات و إحداث التآكل

Author

Muhammad, Inas Qasim

Source

Marsh Bulletin

Issue

Vol. 9, Issue 1 (30 Jun. 2014), pp.49-64, 16 p.

Publisher

University of Basrah College of Science

Publication Date

2014-06-30

Country of Publication

Iraq

No. of Pages

16

Main Subjects

Mechanical Engineering

Topics

Abstract AR

إن الهدف من هذه الدراسة هو لاختبار إمكانية المياه المستعملة في منظومة تبريد محطة توليد كهرباء النجيبية، البصرة .على تكوين الترسبات و على أحداث التآكل داخل أنابيب التبريد و لهذا الغرض فقد تم استخدام دلائل استقرارية الماء مثل Langelier saturation index,Ryznar stability index, Puckurius scaling index and Larson Ratio index لاختبار هذه القدرة.

تم حساب هذه الدلائل للماء قيد الدراسة بالاعتماد على النتائج المستحصلة من القياسات الحقلية للماء المستعمل في منظومة التبريد في المحطة للفترة من كانون الثاني 2012 إلى كانون الأول 2012، وقد تم تطبيق التحاليل الكمية في قياس المتغيرات للماء قيد الدراسة و كان معدل قيم الدليل Langelir index (-0.3317) و معدل قيم الدليل Ryznar index (7.7833)، و معدل قيم الدليل Puckurius index (6.216) أما معدل قيم الدليل Larson Ratio (29.59) و استنادا للنتائج المستحصلة فلقد تم إثبات أن الماء المستخدم في منظومة التبريد في محطة توليد كهرباء النجيبية له الميل لتكوين الترسبات و أيضا له القدرة على إحداث التآكل في أنابيب المنظومة، وعند إجراء دراسة إحصائية للنتائج وجد أن هناك علاقة ارتباط بين الدلائل المذكورة أعلاه و بعض تراكيز أيونات المعادن المقاسة.

Abstract EN

The aim of this research is to study the potential of scale formation and corrosivity of the water using in Al-Najebia power station cooling system in Basrah province, south Iraq.

Water indices such as langelier saturation index, Ryznar stability index, Pukuriuos scaling index and Larson ratio have been used for predicting the corrosive, scale forming .

The study is based on the obtained corrosion and scale data for the period from Jan.

2012 to Dec.

2012, samples were collected from Al-Najebia Power Station cooling system water, the analytical results were used to calculate the indices, because of seasonal flucations in water characteristics, sampling was performed twice monthly.

The quantitative analytical methods were employed.

All indices were calculated the mean values of langelier saturation index (-0.3317), Ryznar stability index mean value was (7.7833), Puckurius scaling index mean value was (6.216) while the mean value of Larson Ratio was (29.59) and preliminary results confirmed that the studied water has a tendency to corrosion and scale formation, also the results revealed that the indices were correlated with measured metal ions.

American Psychological Association (APA)

Muhammad, Inas Qasim. 2014. Assessment the potential of scale formation and the corrosivity of Al-Najebia thermal power plant cooling system water. Marsh Bulletin،Vol. 9, no. 1, pp.49-64.
https://search.emarefa.net/detail/BIM-387219

Modern Language Association (MLA)

Muhammad, Inas Qasim. Assessment the potential of scale formation and the corrosivity of Al-Najebia thermal power plant cooling system water. Marsh Bulletin Vol. 9, no. 1 (2014), pp.49-64.
https://search.emarefa.net/detail/BIM-387219

American Medical Association (AMA)

Muhammad, Inas Qasim. Assessment the potential of scale formation and the corrosivity of Al-Najebia thermal power plant cooling system water. Marsh Bulletin. 2014. Vol. 9, no. 1, pp.49-64.
https://search.emarefa.net/detail/BIM-387219

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references : p. 63-64

Record ID

BIM-387219