Abstract AR
يتناول هذا البحث دراسة الخواص المختلفة لأنواع متعددة من التربة، لدراسة تكون طبقات مجففة حول كابلات القوى الكهربائية الأرضية، و قد أخذ في الاعتبار خواص التربة من حيث الثقل النوعي للتربة و التدرج الحبيبي و درجة التماسك و احتفاظها بالرطوبة.
و من المعروف أن التيار المار في الكابلات الكهربائية المدفونة في التربة يعتمد على أقصى درجة حرارة للموصل، و يعتمد أيضا على المقاومات الحرارية للطبقات المختلفة المحيطة به، و على وجه الخصوص المقاومة الحرارية للتربة.
و قد لوحظ أن تكون الطبقات المجففة حول الكابلات المدفونة تبدأ في التكون عند درجة حرارة 54 درجة مئوية في بعض أنواع التربة، و تبدأ عند 57 درجة مئوية في البعض الآخر، و ذلك اعتمادا على سرعة فقد التربة لبخار الماء.
و قد أجريت دراسة معملية على كابل جهد متوسط ثلاثي الأطوار محمل في الشبكة و مدفون على عمق مائة سنتيمتر من سطح الأرض، و تم دراسة : 1- التوزيع الحراري فوق السطح الخارجي للكابل على مدار علم 1991م.
2- التغير في درجة حرارة الجو المحيط عند سطح التربة.
3- توزيع الرطوبة حول الكابل على مدار السنة.
4- أقصى أحمال على مدار السنة.
و قد تم التعرف على السلوك الحراري للتربة من خلال القياسات، و تم تحديد زمن تكون طبقات جافة حول الكابلات.
Abstract EN
Six types of soil were investigated for studying the drying-out phenomenon and the thermal behaviour of the soil around high power cables.
Specific gravity, grain size distribution, permeability and compaction tests were carried out for six types of soil.
The measured pF-curves and the recorded distributions of temperature with both time and distance at the stated conditions are presented.
Also, the distributions of moisture with distance are given.
From the analysis of the temperature distributions with both time and distance; it was found that the temperatures of some soil points are rapidly increased.
From the analysis of the measured distributions of moisture with distance, it was also found that all soil points of rapidly increased temperature had approximately zero moisture content.
So, the discontinuity found at the measured temperature distributions curves indicated the separation between two zones with high respectively low thermal resistivities or with dry respectively moist soil.
Drying-out phenomenon started at 54°C in sand 2 and at 57°C in sands 1 and 3.
During heating processes, it was noticed that some types of sand lose their moisture content faster than other sand types.
American Psychological Association (APA)
Jawdah, Usamah al-Sayyid& Abd al-Aziz, Abd al-Aziz Mahmud& Rifai, Ahmad Rifai& Matar, Zaki. 1997. Experimental study for drying-out of soil around underground power cables. Journal of King Abdulaziz University : Engineering Sciences،Vol. 9, no. 1, pp.23-40.
https://search.emarefa.net/detail/BIM-394422
Modern Language Association (MLA)
Rifai, Ahmad Rifai…[et al.]. Experimental study for drying-out of soil around underground power cables. Journal of King Abdulaziz University : Engineering Sciences Vol. 9, no. 1 (1997), pp.23-40.
https://search.emarefa.net/detail/BIM-394422
American Medical Association (AMA)
Jawdah, Usamah al-Sayyid& Abd al-Aziz, Abd al-Aziz Mahmud& Rifai, Ahmad Rifai& Matar, Zaki. Experimental study for drying-out of soil around underground power cables. Journal of King Abdulaziz University : Engineering Sciences. 1997. Vol. 9, no. 1, pp.23-40.
https://search.emarefa.net/detail/BIM-394422
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references : p.38-39
Record ID
BIM-394422