Statistics Analysis Measures Painting of Cooling Tower
Joint Authors
Zacharopoulou, E.
Batis, G.
Zacharopoulou, A.
Source
International Journal of Corrosion
Issue
Vol. 2013, Issue 2013 (31 Dec. 2013), pp.1-9, 9 p.
Publisher
Hindawi Publishing Corporation
Publication Date
2013-12-16
Country of Publication
Egypt
No. of Pages
9
Main Subjects
Abstract EN
This study refers to the cooling tower of Megalopolis (construction 1975) and protection from corrosive environment.
The maintenance of the cooling tower took place in 2008.
The cooling tower was badly damaged from corrosion of reinforcement.
The parabolic cooling towers (factory of electrical power) are a typical example of construction, which has a special aggressive environment.
The protection of cooling towers is usually achieved through organic coatings.
Because of the different environmental impacts on the internal and external side of the cooling tower, a different system of paint application is required.
The present study refers to the damages caused by corrosion process.
The corrosive environments, the application of this painting, the quality control process, the measures and statistics analysis, and the results were discussed in this study.
In the process of quality control the following measurements were taken into consideration: (1) examination of the adhesion with the cross-cut test, (2) examination of the film thickness, and (3) controlling of the pull-off resistance for concrete substrates and paintings.
Finally, this study refers to the correlations of measurements, analysis of failures in relation to the quality of repair, and rehabilitation of the cooling tower.
Also this study made a first attempt to apply the specific corrosion inhibitors in such a large structure.
American Psychological Association (APA)
Zacharopoulou, A.& Zacharopoulou, E.& Batis, G.. 2013. Statistics Analysis Measures Painting of Cooling Tower. International Journal of Corrosion،Vol. 2013, no. 2013, pp.1-9.
https://search.emarefa.net/detail/BIM-468206
Modern Language Association (MLA)
Zacharopoulou, A.…[et al.]. Statistics Analysis Measures Painting of Cooling Tower. International Journal of Corrosion No. 2013 (2013), pp.1-9.
https://search.emarefa.net/detail/BIM-468206
American Medical Association (AMA)
Zacharopoulou, A.& Zacharopoulou, E.& Batis, G.. Statistics Analysis Measures Painting of Cooling Tower. International Journal of Corrosion. 2013. Vol. 2013, no. 2013, pp.1-9.
https://search.emarefa.net/detail/BIM-468206
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references
Record ID