Condition Evaluation of Large Generator Stator Insulation Based on Partial Discharge Measurement
Joint Authors
Hu, Bo
Pan, Ling
Yan, Chen
Li, Ruihua
Li, Hao
Source
Advances in Mechanical Engineering
Issue
Vol. 2013, Issue 2013 (31 Dec. 2013), pp.1-10, 10 p.
Publisher
Hindawi Publishing Corporation
Publication Date
2013-08-27
Country of Publication
Egypt
No. of Pages
10
Main Subjects
Abstract EN
The large generator faults are mostly from the stator insulation, which is aged by exposure to a combination of thermal, electrical, mechanical, and harsh environment stresses.
Condition evaluation of stator insulation is an important measure of ensuring the safe operation and extending the remaining life of large generator.
In this paper, a diagnosis method based on the partial discharge (PD) measurement was used for the condition evaluation of the stator insulation.
The statistical parameters of partial discharge phase resolved distribution were proposed to assess the aging condition of stator insulation.
A partial least square (PLS) approach was used to explore and extract relationships between the statistical parameters of partial discharge distribution with physical properties and performance such as electrical breakdown strength.
Results of the PD testing and statistical analysis show that the statistical parameter Sk extent of partial discharge distribution changes much more remarkably with the aging time than do the other parameters.
The statistical parameter Sk can be considered as a potential indicator of stator insulation aging.
The PLS approach can effectively assess the stator insulation aging condition and can provide a predictive capability for the stator insulation diagnosis.
American Psychological Association (APA)
Li, Ruihua& Pan, Ling& Yan, Chen& Li, Hao& Hu, Bo. 2013. Condition Evaluation of Large Generator Stator Insulation Based on Partial Discharge Measurement. Advances in Mechanical Engineering،Vol. 2013, no. 2013, pp.1-10.
https://search.emarefa.net/detail/BIM-497060
Modern Language Association (MLA)
Li, Ruihua…[et al.]. Condition Evaluation of Large Generator Stator Insulation Based on Partial Discharge Measurement. Advances in Mechanical Engineering No. 2013 (2013), pp.1-10.
https://search.emarefa.net/detail/BIM-497060
American Medical Association (AMA)
Li, Ruihua& Pan, Ling& Yan, Chen& Li, Hao& Hu, Bo. Condition Evaluation of Large Generator Stator Insulation Based on Partial Discharge Measurement. Advances in Mechanical Engineering. 2013. Vol. 2013, no. 2013, pp.1-10.
https://search.emarefa.net/detail/BIM-497060
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references
Record ID
BIM-497060