Reliability evaluation of multi-terminals VSC-HVDC system

Joint Authors

Chen, Peng
Dong, Jizhe

Source

Journal of Electrical Systems

Issue

Vol. 11, Issue 3 (30 Sep. 2015), pp.442-452, 11 p.

Publisher

Piercing Star House

Publication Date

2015-09-30

Country of Publication

Algeria

No. of Pages

11

Main Subjects

Electronic engineering

Topics

Abstract EN

Reliability evaluation of VSC-HVDC system with multi-terminals has received very little attention in the past.

In this paper, an equivalent model is developed for evaluating the reliability of VSC-HVDC system, especially multi-terminals VSC-HVDC system.

Using the reliability engineering concepts, such as the method of component equivalents and the frequency and duration method, some reliability indices, such as forced outage rate and frequency of each terminal, are calculated and the capacity outage probability table can also be obtained.

Case studies are numerically applied on two VSC-HVDC systems which have different terminals and results are analyzed.

At last, sensitivity analyses for forced outage rate and frequency with respect to the failure rate of different components are conducted.

American Psychological Association (APA)

Dong, Jizhe& Chen, Peng. 2015. Reliability evaluation of multi-terminals VSC-HVDC system. Journal of Electrical Systems،Vol. 11, no. 3, pp.442-452.
https://search.emarefa.net/detail/BIM-610450

Modern Language Association (MLA)

Dong, Jizhe& Chen, Peng. Reliability evaluation of multi-terminals VSC-HVDC system. Journal of Electrical Systems Vol. 11, no. 3 (Sep. 2015), pp.442-452.
https://search.emarefa.net/detail/BIM-610450

American Medical Association (AMA)

Dong, Jizhe& Chen, Peng. Reliability evaluation of multi-terminals VSC-HVDC system. Journal of Electrical Systems. 2015. Vol. 11, no. 3, pp.442-452.
https://search.emarefa.net/detail/BIM-610450

Data Type

Journal Articles

Language

English

Notes

Includes bibliographical references : p. 452

Record ID

BIM-610450