Sub-cooling auxiliary system for performance enhancement of main refrigeration system
Other Title(s)
استخدام منظومة تبريد مفرط ثانوية لتحسين أداء منظومات التبريد الرئيسية
Joint Authors
Hamad, Ahmad J.
Hamad Allah, Mustafa W.
Husayn, Fawziyah M.
Source
Engineering and Technology Journal
Issue
Vol. 33, Issue 8A (31 Aug. 2015), pp.1798-1813, 16 p.
Publisher
Publication Date
2015-08-31
Country of Publication
Iraq
No. of Pages
16
Main Subjects
Topics
Abstract EN
In present work, a sub-cooling auxiliary system is integrated with vapour compression refrigeration system to predict the performance characteristics and energy saving of the system.
An experimental investigation was performed to determine the performance parameters at various operating conditions using two types of refrigerants, R-134a and zeotropic mixed refrigerant R-404A.
Investigating the results has showed that, the enhancement in performance of the refrigeration system with sub-cooling circuit compared with that for system without sub-cooling for R-134a was about 5% increase in RE, 14% optimization in COP and 2.8% energy saving for different thermal loads applied on the evaporator.
While for R-404A, the increase in RE was 4%, the optimization in COP was about 13% and 3.7% energy saving.
There is a significant improvement in the performance of the system with R-404A compared with that for R-134a at the same operating conditions.
American Psychological Association (APA)
Hamad, Ahmad J.& Husayn, Fawziyah M.& Hamad Allah, Mustafa W.. 2015. Sub-cooling auxiliary system for performance enhancement of main refrigeration system. Engineering and Technology Journal،Vol. 33, no. 8A, pp.1798-1813.
https://search.emarefa.net/detail/BIM-655596
Modern Language Association (MLA)
Hamad, Ahmad J.…[et al.]. Sub-cooling auxiliary system for performance enhancement of main refrigeration system. Engineering and Technology Journal Vol. 33, no. 8A (2015), pp.1798-1813.
https://search.emarefa.net/detail/BIM-655596
American Medical Association (AMA)
Hamad, Ahmad J.& Husayn, Fawziyah M.& Hamad Allah, Mustafa W.. Sub-cooling auxiliary system for performance enhancement of main refrigeration system. Engineering and Technology Journal. 2015. Vol. 33, no. 8A, pp.1798-1813.
https://search.emarefa.net/detail/BIM-655596
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references : p. 1812-1813
Record ID
BIM-655596