![](/images/graphics-bg.png)
Comparison between hand calculation and HAP programs for estimating total cooling load for buildings
Joint Authors
Muhammad, Azhar Karim
Abd Allah, Ranj Sirwan
Mari, Id Iqab
Source
ZANCO Journal of Pure and Applied Sciences
Issue
Vol. 28, Issue 4 (31 Aug. 2016), pp.90-96, 7 p.
Publisher
Salahaddin University-Erbil Department of Scientific Publications
Publication Date
2016-08-31
Country of Publication
Iraq
No. of Pages
7
Main Subjects
Abstract EN
The purpose of this paper is to compare between (hand calculation) and HAP programs for building cooling load for thermal comfort, humidity comfort, ventilation, and air filtration.
This project is developed to find the best way to apply the concept of (HVAC) system design in Erbil Polytechnic University/ Refrigeration and Air-conditioning Engineering Department.HAP uses the ASHRAE transfer function method for load calculations and detailed 8,760 hour-by-hour simulation techniques for the energy analysis.
The aim of this study is to calculate and compare between hand calculations and HAP program.
The building consists of two storeys with 19 zones to be conditioned.
The international standard is used in the presented study.
This paper estimates the cooling load for different climate conditions by using CLTD method for the building.
Cooling load such as, people, lighting, infiltration and ventilation heat gain can be easily entered to the MS-Excel program.
In addition to other data such as the cooling loads due to walls and roofs.
The results show that there are similarities between the two methods.
The maximum total cooling load deference between hand calculation and HAP program is 2.1 %.
Therefore, the hourly analysis program can be used for any building design to calculate the load and select the systems.
American Psychological Association (APA)
Muhammad, Azhar Karim& Abd Allah, Ranj Sirwan& Mari, Id Iqab. 2016. Comparison between hand calculation and HAP programs for estimating total cooling load for buildings. ZANCO Journal of Pure and Applied Sciences،Vol. 28, no. 4, pp.90-96.
https://search.emarefa.net/detail/BIM-762115
Modern Language Association (MLA)
Muhammad, Azhar Karim…[et al.]. Comparison between hand calculation and HAP programs for estimating total cooling load for buildings. ZANCO Journal of Pure and Applied Sciences Vol. 28, no. 4 (2016), pp.90-96.
https://search.emarefa.net/detail/BIM-762115
American Medical Association (AMA)
Muhammad, Azhar Karim& Abd Allah, Ranj Sirwan& Mari, Id Iqab. Comparison between hand calculation and HAP programs for estimating total cooling load for buildings. ZANCO Journal of Pure and Applied Sciences. 2016. Vol. 28, no. 4, pp.90-96.
https://search.emarefa.net/detail/BIM-762115
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references : p. 96
Record ID