Experimental investigation for the thermal performance of modified closed wet cooling tower

Other Title(s)

التحقيق العملي للأداء الحراري على برج تبريد رطب مغلق مطور

Joint Authors

Jaffal, Haydar Muhammad
Mahdi, Qasim Salih

Source

Nahrain University-College of Engineering Journal

Issue

Vol. 19, Issue 2 (31 Dec. 2016), pp.310-326, 17 p.

Publisher

Nahrain University College of Engineering

Publication Date

2016-12-31

Country of Publication

Iraq

No. of Pages

17

Main Subjects

Engineering & Technology Sciences (Multidisciplinary)

Abstract EN

Researchers and designers keenly seek to improve the performance of cooling towers because of the extensive impact on the work and efficiency of the systems concerned to these towers.

For this purpose, a Closed Wet Cooling Tower (CWCT) modified with added packing was designed, manufactured and tested for cooling capacity of 9 kW in Iraq.

A series of experiments was carried out at different operational and conformational parameters.

Operational parameters demonstrate: air flow rate, spray water flow rate, cooling water flow rate, inlet cooling water temperature and inlet air wet bulb temperature.

Conformational parameters indicate: height of packing used and location of packing.

The results showed a significant performance improvement when using packing with CWCT under the heat exchanger and above the heat exchanger as compared to CWCT.

Empirical correlations are obtained to predict water film heat transfer coefficient and air-water mass transfer coefficient considering the influences of operational parameters.

American Psychological Association (APA)

Mahdi, Qasim Salih& Jaffal, Haydar Muhammad. 2016. Experimental investigation for the thermal performance of modified closed wet cooling tower. Nahrain University-College of Engineering Journal،Vol. 19, no. 2, pp.310-326.
https://search.emarefa.net/detail/BIM-819163

Modern Language Association (MLA)

Mahdi, Qasim Salih& Jaffal, Haydar Muhammad. Experimental investigation for the thermal performance of modified closed wet cooling tower. Nahrain University-College of Engineering Journal Vol. 19, no. 2 (Dec. 2016), pp.310-326.
https://search.emarefa.net/detail/BIM-819163

American Medical Association (AMA)

Mahdi, Qasim Salih& Jaffal, Haydar Muhammad. Experimental investigation for the thermal performance of modified closed wet cooling tower. Nahrain University-College of Engineering Journal. 2016. Vol. 19, no. 2, pp.310-326.
https://search.emarefa.net/detail/BIM-819163

Data Type

Journal Articles

Language

English

Notes

Record ID

BIM-819163