Study the effect of the flow on the performance of a shell and tube type heat exchanger using experimental design technique

Other Title(s)

دراسة تأثير الجريان على أداء مبادل حراري نوع غلاف و أنبوب باستعمال تقنية تصميم التجارب

Joint Authors

Farhan, Sad Sami
Abd Allah, Zuhayr Hasan
Salim, Thamir Khalaf

Source

Tikrit Journal of Engineering Sciences

Issue

Vol. 23, Issue 2 (30 Jun. 2016), pp.38-45, 8 p.

Publisher

Tikrit University Colleg of Engineering

Publication Date

2016-06-30

Country of Publication

Iraq

No. of Pages

8

Main Subjects

Mechanical Engineering

Abstract EN

In the current research an experimental study was done to show the effect of pulse flow on the effectiveness of shell and tube type heat exchanger.

the study was in the case of steady and pulse flows with a changing mass flow rate of hot water flowing inside the pipes of the heat exchanger for the range between (0.0273-0.0819 kg / s) at fix mass flow rate of cold water that flows through the shell and on the outer surface of the pipes when (0.0416 kg / s), to obtain pulsing a used was solenoid valve.

The research aims to measure the percentage effect of independent factors which were presenting the mass flow rate of hot water, flow type and the surrounding environment conditions of the experimental side upon shell and tube type heat exchanger performance using experimental design technique at the significant level (0.05).The results derived from the experimental tests showed that pulse flow leads to increase internal heat transfer coefficient (hi) comparing with its value in the steady flow and the highest increase was by (9.75%) at a mass flow rate of hot water (0.0416 kg / s) and increases the overall heat transfer coefficient (U), where the highest percentage was by )4.68%) at a mass flow rate of hot water (0.0416kg/s).

The results also showed increasing both the number of transmitted units (NTU) and the effectiveness of the shell and tube type heat exchanger ( ) in the case of pulse flow of its value in the steady flow and the highest percentage of increase occurring was (4.75%) and (1.85%), respectively, and at the mass flow rate of hot water (0.0416 kg / s).

Percentage effect of mass flow rate of hot water was (97%, 97.42%, 95.5%, 99.48%) and the percentage effect of each flow type and the errors were (2.8%, 2.25%, 2.44%, 0.4%) and (0.

2, 0.33%, 2.06%, 0.12) respectively.

American Psychological Association (APA)

Abd Allah, Zuhayr Hasan& Farhan, Sad Sami& Salim, Thamir Khalaf. 2016. Study the effect of the flow on the performance of a shell and tube type heat exchanger using experimental design technique. Tikrit Journal of Engineering Sciences،Vol. 23, no. 2, pp.38-45.
https://search.emarefa.net/detail/BIM-936925

Modern Language Association (MLA)

Abd Allah, Zuhayr Hasan…[et al.]. Study the effect of the flow on the performance of a shell and tube type heat exchanger using experimental design technique. Tikrit Journal of Engineering Sciences Vol. 23, no. 2 (2016), pp.38-45.
https://search.emarefa.net/detail/BIM-936925

American Medical Association (AMA)

Abd Allah, Zuhayr Hasan& Farhan, Sad Sami& Salim, Thamir Khalaf. Study the effect of the flow on the performance of a shell and tube type heat exchanger using experimental design technique. Tikrit Journal of Engineering Sciences. 2016. Vol. 23, no. 2, pp.38-45.
https://search.emarefa.net/detail/BIM-936925

Data Type

Journal Articles

Language

English

Notes

Record ID

BIM-936925