Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications
العناوين الأخرى
تأثير نسبت المليء على درجت حرارة المبخر في الثرمسيفون الحلقي المستخدم في تطبيقات التبريد الإلكترونية
المؤلفون المشاركون
al-Tabakh, Awf Abd al-Rahman Ahmad
Abd al-Rasul, Adnan Abd al-Amir
Adnan, Samah Ihsan
المصدر
Journal of Engineering and Sustainable Development
العدد
المجلد 24، العدد 2 (31 مارس/آذار 2020)، ص ص. 18-29، 12ص.
الناشر
الجامعة المستنصرية كلية الهندسة
تاريخ النشر
2020-03-31
دولة النشر
العراق
عدد الصفحات
12
التخصصات الرئيسية
الموضوعات
الملخص EN
This; paper; presents; the; effect; of; filling; ratio; on; thermal; performance; of; a; loop; thermosyphon.
The experimental setup consists of an evaporator, a condenser, a riser and a downcomer.
The dimensions of the loop thermosyphon under consideration were chosen so that they are mostly suitable for use in the cooling of electronic components.
Distilled water was used as a working fluid.
Experiments were carried out to estimate the performance of the loop thermosyphon for a range of input power from 10 to 100 W.
Four fill ratios were considered in the present work, namely; 15% , 25% , 50% and 85% .
Results showed that the maximum value of wall temperature in evaporator was 95°C, at 100 W input power and 15% fill ratio.
The fill ratio of 50% gave the minimum evaporator wall temperature which was 80°C.
Increasing fill ratio tends to decrease the evaporator wall temperature for This; paper; presents; the; effect; of; filling; ratio; on; thermal; performance; of; a; loop; thermosyphon.
The experimental setup consists of an evaporator, a condenser, a riser and a downcomer.
The dimensions of the loop thermosyphon under consideration were chosen so that they are mostly suitable for use in the cooling of electronic components.
Distilled water was used as a working fluid.
Experiments were carried out to estimate the performance of the loop thermosyphon for a range of input power from 10 to 100 W.
Four fill ratios were considered in the present work, namely; 15% , 25% , 50% and 85% .
Results showed that the maximum value of wall temperature in evaporator was 95°C, at 100 W input power and 15% fill ratio.
The fill ratio of 50% gave the minimum evaporator wall temperature which was 80°C.
Increasing fill ratio tends to decrease the evaporator wall temperature for evaporator.
نمط استشهاد جمعية علماء النفس الأمريكية (APA)
Adnan, Samah Ihsan& al-Tabakh, Awf Abd al-Rahman Ahmad& Abd al-Rasul, Adnan Abd al-Amir. 2020. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development،Vol. 24, no. 2, pp.18-29.
https://search.emarefa.net/detail/BIM-1263684
نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)
Adnan, Samah Ihsan…[et al.]. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development Vol. 24, no. 2 (Mar. 2020), pp.18-29.
https://search.emarefa.net/detail/BIM-1263684
نمط استشهاد الجمعية الطبية الأمريكية (AMA)
Adnan, Samah Ihsan& al-Tabakh, Awf Abd al-Rahman Ahmad& Abd al-Rasul, Adnan Abd al-Amir. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development. 2020. Vol. 24, no. 2, pp.18-29.
https://search.emarefa.net/detail/BIM-1263684
نوع البيانات
مقالات
لغة النص
الإنجليزية
الملاحظات
-
رقم السجل
BIM-1263684
قاعدة معامل التأثير والاستشهادات المرجعية العربي "ارسيف Arcif"
أضخم قاعدة بيانات عربية للاستشهادات المرجعية للمجلات العلمية المحكمة الصادرة في العالم العربي
تقوم هذه الخدمة بالتحقق من التشابه أو الانتحال في الأبحاث والمقالات العلمية والأطروحات الجامعية والكتب والأبحاث باللغة العربية، وتحديد درجة التشابه أو أصالة الأعمال البحثية وحماية ملكيتها الفكرية. تعرف اكثر