Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications

Other Title(s)

تأثير نسبت المليء على درجت حرارة المبخر في الثرمسيفون الحلقي المستخدم في تطبيقات التبريد الإلكترونية

Joint Authors

al-Tabakh, Awf Abd al-Rahman Ahmad
Abd al-Rasul, Adnan Abd al-Amir
Adnan, Samah Ihsan

Source

Journal of Engineering and Sustainable Development

Issue

Vol. 24, Issue 2 (31 Mar. 2020), pp.18-29, 12 p.

Publisher

al-Mustansyriah University College of Engineering

Publication Date

2020-03-31

Country of Publication

Iraq

No. of Pages

12

Main Subjects

Mechanical Engineering

Topics

Abstract EN

This; paper; presents; the; effect; of; filling; ratio; on; thermal; performance; of; a; loop; thermosyphon.

The experimental setup consists of an evaporator, a condenser, a riser and a downcomer.

The dimensions of the loop thermosyphon under consideration were chosen so that they are mostly suitable for use in the cooling of electronic components.

Distilled water was used as a working fluid.

Experiments were carried out to estimate the performance of the loop thermosyphon for a range of input power from 10 to 100 W.

Four fill ratios were considered in the present work, namely; 15% , 25% , 50% and 85% .

Results showed that the maximum value of wall temperature in evaporator was 95°C, at 100 W input power and 15% fill ratio.

The fill ratio of 50% gave the minimum evaporator wall temperature which was 80°C.

Increasing fill ratio tends to decrease the evaporator wall temperature for This; paper; presents; the; effect; of; filling; ratio; on; thermal; performance; of; a; loop; thermosyphon.

The experimental setup consists of an evaporator, a condenser, a riser and a downcomer.

The dimensions of the loop thermosyphon under consideration were chosen so that they are mostly suitable for use in the cooling of electronic components.

Distilled water was used as a working fluid.

Experiments were carried out to estimate the performance of the loop thermosyphon for a range of input power from 10 to 100 W.

Four fill ratios were considered in the present work, namely; 15% , 25% , 50% and 85% .

Results showed that the maximum value of wall temperature in evaporator was 95°C, at 100 W input power and 15% fill ratio.

The fill ratio of 50% gave the minimum evaporator wall temperature which was 80°C.

Increasing fill ratio tends to decrease the evaporator wall temperature for evaporator.

American Psychological Association (APA)

Adnan, Samah Ihsan& al-Tabakh, Awf Abd al-Rahman Ahmad& Abd al-Rasul, Adnan Abd al-Amir. 2020. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development،Vol. 24, no. 2, pp.18-29.
https://search.emarefa.net/detail/BIM-1263684

Modern Language Association (MLA)

Adnan, Samah Ihsan…[et al.]. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development Vol. 24, no. 2 (Mar. 2020), pp.18-29.
https://search.emarefa.net/detail/BIM-1263684

American Medical Association (AMA)

Adnan, Samah Ihsan& al-Tabakh, Awf Abd al-Rahman Ahmad& Abd al-Rasul, Adnan Abd al-Amir. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development. 2020. Vol. 24, no. 2, pp.18-29.
https://search.emarefa.net/detail/BIM-1263684

Data Type

Journal Articles

Language

English

Notes

-

Record ID

BIM-1263684