![](/images/graphics-bg.png)
Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair
المؤلفون المشاركون
Agboola, O. Phillips
Atikol, Ugur
Yari, Mortaza
Parham, Kiyan
المصدر
Advances in Mechanical Engineering
العدد
المجلد 2013، العدد 2013 (31 ديسمبر/كانون الأول 2013)، ص ص. 1-8، 8ص.
الناشر
Hindawi Publishing Corporation
تاريخ النشر
2013-10-22
دولة النشر
مصر
عدد الصفحات
8
التخصصات الرئيسية
الملخص EN
The thermodynamic performance of the absorption chiller using (H2O + LiCl) as the working pair was simulated and compared with the absorption chiller using (H2O + LiBr).
The effects of evaporation temperature on the performance coefficient, COP, generation temperature, concentration of strong solution, and flow rate ratio were also analyzed.
At the same condensing and absorbing temperature, the simulating results indicated that the performance coefficient for (H2O + LiCl) is approximately equal to (H2O + LiBr) and the generation temperature was lower than that for (H2O + LiBr).
On the other hand, the exergetic efficiency, ECOP, which is based on the second law of thermodynamics, for the absorption chiller using (H2O + LiCl), was more than the system using (H2O + LiBr) under the same operating conditions.
The absorption chiller cycle was then optimized based on the coefficient of performance.
The results show that the coefficient of performance of the absorption chiller, using (H2O + LiBr) at the optimum conditions, was around 1.5–2% higher than that of (H2O + LiCl).
نمط استشهاد جمعية علماء النفس الأمريكية (APA)
Parham, Kiyan& Atikol, Ugur& Yari, Mortaza& Agboola, O. Phillips. 2013. Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair. Advances in Mechanical Engineering،Vol. 2013, no. 2013, pp.1-8.
https://search.emarefa.net/detail/BIM-490231
نمط استشهاد الجمعية الأمريكية للغات الحديثة (MLA)
Parham, Kiyan…[et al.]. Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair. Advances in Mechanical Engineering No. 2013 (2013), pp.1-8.
https://search.emarefa.net/detail/BIM-490231
نمط استشهاد الجمعية الطبية الأمريكية (AMA)
Parham, Kiyan& Atikol, Ugur& Yari, Mortaza& Agboola, O. Phillips. Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair. Advances in Mechanical Engineering. 2013. Vol. 2013, no. 2013, pp.1-8.
https://search.emarefa.net/detail/BIM-490231
نوع البيانات
مقالات
لغة النص
الإنجليزية
الملاحظات
Includes bibliographical references
رقم السجل
BIM-490231
قاعدة معامل التأثير والاستشهادات المرجعية العربي "ارسيف Arcif"
أضخم قاعدة بيانات عربية للاستشهادات المرجعية للمجلات العلمية المحكمة الصادرة في العالم العربي
![](/images/ebook-kashef.png)
تقوم هذه الخدمة بالتحقق من التشابه أو الانتحال في الأبحاث والمقالات العلمية والأطروحات الجامعية والكتب والأبحاث باللغة العربية، وتحديد درجة التشابه أو أصالة الأعمال البحثية وحماية ملكيتها الفكرية. تعرف اكثر
![](/images/kashef-image.png)