![](/images/graphics-bg.png)
Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair
Joint Authors
Agboola, O. Phillips
Atikol, Ugur
Yari, Mortaza
Parham, Kiyan
Source
Advances in Mechanical Engineering
Issue
Vol. 2013, Issue 2013 (31 Dec. 2013), pp.1-8, 8 p.
Publisher
Hindawi Publishing Corporation
Publication Date
2013-10-22
Country of Publication
Egypt
No. of Pages
8
Main Subjects
Abstract EN
The thermodynamic performance of the absorption chiller using (H2O + LiCl) as the working pair was simulated and compared with the absorption chiller using (H2O + LiBr).
The effects of evaporation temperature on the performance coefficient, COP, generation temperature, concentration of strong solution, and flow rate ratio were also analyzed.
At the same condensing and absorbing temperature, the simulating results indicated that the performance coefficient for (H2O + LiCl) is approximately equal to (H2O + LiBr) and the generation temperature was lower than that for (H2O + LiBr).
On the other hand, the exergetic efficiency, ECOP, which is based on the second law of thermodynamics, for the absorption chiller using (H2O + LiCl), was more than the system using (H2O + LiBr) under the same operating conditions.
The absorption chiller cycle was then optimized based on the coefficient of performance.
The results show that the coefficient of performance of the absorption chiller, using (H2O + LiBr) at the optimum conditions, was around 1.5–2% higher than that of (H2O + LiCl).
American Psychological Association (APA)
Parham, Kiyan& Atikol, Ugur& Yari, Mortaza& Agboola, O. Phillips. 2013. Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair. Advances in Mechanical Engineering،Vol. 2013, no. 2013, pp.1-8.
https://search.emarefa.net/detail/BIM-490231
Modern Language Association (MLA)
Parham, Kiyan…[et al.]. Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair. Advances in Mechanical Engineering No. 2013 (2013), pp.1-8.
https://search.emarefa.net/detail/BIM-490231
American Medical Association (AMA)
Parham, Kiyan& Atikol, Ugur& Yari, Mortaza& Agboola, O. Phillips. Evaluation and Optimization of Single Stage Absorption Chiller Using (LiCl + H2O) as the Working Pair. Advances in Mechanical Engineering. 2013. Vol. 2013, no. 2013, pp.1-8.
https://search.emarefa.net/detail/BIM-490231
Data Type
Journal Articles
Language
English
Notes
Includes bibliographical references
Record ID
BIM-490231