Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications
Other Title(s)
تأثير نسبت المليء على درجت حرارة المبخر في الثرمسيفون الحلقي المستخدم في تطبيقات التبريد الإلكترونية
Joint Authors
al-Tabakh, Awf Abd al-Rahman Ahmad
Abd al-Rasul, Adnan Abd al-Amir
Adnan, Samah Ihsan
Source
Journal of Engineering and Sustainable Development
Issue
Vol. 24, Issue 2 (31 Mar. 2020), pp.18-29, 12 p.
Publisher
al-Mustansyriah University College of Engineering
Publication Date
2020-03-31
Country of Publication
Iraq
No. of Pages
12
Main Subjects
Topics
Abstract EN
This; paper; presents; the; effect; of; filling; ratio; on; thermal; performance; of; a; loop; thermosyphon.
The experimental setup consists of an evaporator, a condenser, a riser and a downcomer.
The dimensions of the loop thermosyphon under consideration were chosen so that they are mostly suitable for use in the cooling of electronic components.
Distilled water was used as a working fluid.
Experiments were carried out to estimate the performance of the loop thermosyphon for a range of input power from 10 to 100 W.
Four fill ratios were considered in the present work, namely; 15% , 25% , 50% and 85% .
Results showed that the maximum value of wall temperature in evaporator was 95°C, at 100 W input power and 15% fill ratio.
The fill ratio of 50% gave the minimum evaporator wall temperature which was 80°C.
Increasing fill ratio tends to decrease the evaporator wall temperature for This; paper; presents; the; effect; of; filling; ratio; on; thermal; performance; of; a; loop; thermosyphon.
The experimental setup consists of an evaporator, a condenser, a riser and a downcomer.
The dimensions of the loop thermosyphon under consideration were chosen so that they are mostly suitable for use in the cooling of electronic components.
Distilled water was used as a working fluid.
Experiments were carried out to estimate the performance of the loop thermosyphon for a range of input power from 10 to 100 W.
Four fill ratios were considered in the present work, namely; 15% , 25% , 50% and 85% .
Results showed that the maximum value of wall temperature in evaporator was 95°C, at 100 W input power and 15% fill ratio.
The fill ratio of 50% gave the minimum evaporator wall temperature which was 80°C.
Increasing fill ratio tends to decrease the evaporator wall temperature for evaporator.
American Psychological Association (APA)
Adnan, Samah Ihsan& al-Tabakh, Awf Abd al-Rahman Ahmad& Abd al-Rasul, Adnan Abd al-Amir. 2020. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development،Vol. 24, no. 2, pp.18-29.
https://search.emarefa.net/detail/BIM-1263684
Modern Language Association (MLA)
Adnan, Samah Ihsan…[et al.]. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development Vol. 24, no. 2 (Mar. 2020), pp.18-29.
https://search.emarefa.net/detail/BIM-1263684
American Medical Association (AMA)
Adnan, Samah Ihsan& al-Tabakh, Awf Abd al-Rahman Ahmad& Abd al-Rasul, Adnan Abd al-Amir. Effect of fill ratio on evaporator wall temperature in a loop thermosyphon used in electronic cooling applications. Journal of Engineering and Sustainable Development. 2020. Vol. 24, no. 2, pp.18-29.
https://search.emarefa.net/detail/BIM-1263684
Data Type
Journal Articles
Language
English
Notes
-
Record ID
BIM-1263684